SIEMENS 6AG1340-1AH02-2AE0
- EICHLER-art.no.: K0169933
- EAN: 4025515144113
- UPC: 662643024272
Product description
SIPLUS S7-300 CP340 RS 232 -25 ... +70 DEGREES C BASED ON 6ES7340-1AH01-0AE0 . COMMUNICATIONS PROCESSOR WITH RS232C-INTERFACE (V.24) INCL. CONFIGURING PACKAGE ON CD
Services for SIEMENS 6AG1340-1AH02-2AE0
Repair
from 646,27 €
to 950,40 €
Replacement
Used
New
1.266,20 €
1.202,89 €
SIEMENS |
6AG1340-1AH02-2AE0 –
additional product information
| Delivery information | |||
|---|---|---|---|
| Export identifier | AL: N ECCN: N | ||
| Net weight | 0.362 | ||
| Quantity | 1 Stück | ||
| Packaging quantity | 1 | ||
| Additional product information | |||
|---|---|---|---|
| Product status | |||
| EAN | 4025515144113 | ||
| UPC | 662643024272 | ||
| Static lot number | 85389091 | ||
| List indicator | A&DSE/SIP ADD | ||
| Product group | 4398 | ||
| Country of origin | DE | ||
| Compliance with the substance restrictions according to RoHS directive | Since: 20120101 | ||
| Product classifications | Version | Classification | |
|---|---|---|---|
| eClass | 4 | 27-24-03-09 | |
| eClass | 5.1 | 27-24-22-08 | |
| eClass | 6.0 | 27-24-22-08 | |
| ETIM | 3 | / | |
| ETIM | 4 | EC001423 | |
| ETIM | 5 | EC001423 | |
| Attribute | Value |
|---|---|
| General information | |
| based on | 6ES7340-1AH02-0AE0 |
| Supply voltage | |
| Rated value (DC) | |
| ● 24 V DC | No; Power supply via backplane bus 5V |
| Input current | |
| from backplane bus 5 V DC, max. | 165 mA |
| Power loss | |
| Power loss, typ. | 0.6 W |
| Power loss, max. | 0.85 W |
| Interfaces | |
| Interfaces/bus type | RS 232C (V.24) |
| Number of interfaces | 1; Isolated |
| Transmission rate, min. | 2.4 kbit/s |
| Transmission rate, max. | 19.2 kbit/s |
| Point-to-point connection | |
| ● Cable length, max. | 15 m |
| ● supported printers | HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined |
| ● Connector type | 9-pin sub D connector |
| Integrated protocol driver | |
| — 3964 (R) | Yes |
| — ASCII | Yes |
| — RK 512 | No |
| — customer-specific drivers reloadable | No |
| Telegram length, max. | |
| — 3964 (R) | 1 024 byte |
| — ASCII | 1 024 byte |
| Transmission speed, RS 232 | |
| — with 3964 (R) protocol, max. | 19.2 kbit/s |
| — with ASCII protocol, max. | 9.6 kbit/s |
| — with printer driver, max. | 9.6 kbit/s |
| Interrupts/diagnostics/status information | |
| Diagnostics indication LED | |
| ● Receive RxD | Yes |
| ● Transmit TxD | Yes |
| ● Group error SF (red) | Yes |
| Standards, approvals, certificates | |
| CE mark | Yes |
| UL approval | Yes; File E239877 |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| Ambient conditions | |
| Ambient temperature during operation | |
| ● min. | -25 °C; = Tmin |
| ● max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
| Ambient temperature during storage/transportation | |
| ● min. | -40 °C |
| ● max. | 70 °C |
| Altitude during operation relating to sea level | |
| ● Installation altitude above sea level, max. | 5 000 m |
| ● Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
| Relative humidity | |
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
| Resistance | |
| Use in stationary industrial systems | |
| — to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| — to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| — to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * |
| Use on ships/at sea | |
| — to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request |
| — to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * |
| — to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * |
| Usage in industrial process technology | |
| — Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) |
| — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) |
| Remark | |
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! |
| Software | |
| Block | |
| ● FB length in RAM, max. | 2 700 byte; Data communication, sending and receiving |
| Connection method | |
| Design of electrical connection for supply voltage | Over backplane bus |
| Dimensions | |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 120 mm |
| Weights | |
| Weight, approx. | 300 g |