| General technical data |
|
| product brand name |
SIRIUS |
| product designation |
Soft starter |
| product feature |
|
| ● integrated bypass contact system |
Yes |
| ● thyristors |
Yes |
| product function |
|
| ● intrinsic device protection |
No |
| ● motor overload protection |
No |
| ● evaluation of thermistor motor protection |
No |
| ● external reset |
No |
| ● adjustable current limitation |
No |
| ● inside-delta circuit |
No |
| product component motor brake output |
No |
| insulation voltage rated value |
600 V |
| degree of pollution |
3, acc. to IEC 60947-4-2 |
| blocking voltage of the thyristor maximum |
1 200 V |
| reference code according to EN 61346-2 |
Q |
| reference code according to DIN 40719 extended according to IEC 204-2 according to IEC 750 |
G |
| Power Electronics |
|
| operational current |
|
| ● at 40 °C rated value |
17.6 A |
| ● at 50 °C rated value |
17 A |
| ● at 60 °C rated value |
14 A |
| yielded mechanical performance for 3-phase motors |
|
| ● at 230 V |
|
| — at standard circuit at 40 °C rated value |
4 kW |
| ● at 400 V |
|
| — at standard circuit at 40 °C rated value |
7.5 kW |
| yielded mechanical performance [hp] for 3-phase AC motor at 200/208 V at standard circuit at 50 °C rated value |
3 hp |
| operating frequency rated value |
50 ... 60 Hz |
| relative negative tolerance of the operating frequency |
-10 % |
| relative positive tolerance of the operating frequency |
10 % |
| operating voltage at standard circuit rated value |
200 ... 480 V |
| relative negative tolerance of the operating voltage at standard circuit |
-15 % |
| relative positive tolerance of the operating voltage at standard circuit |
10 % |
| minimum load [%] |
10 % |
| continuous operating current [% of Ie] at 40 °C |
115 % |
| power loss [W] at operational current at 40 °C during operation typical |
4 W |
| Control circuit/ Control |
|
| type of voltage of the control supply voltage |
AC/DC |
| control supply voltage frequency 1 rated value |
50 Hz |
| control supply voltage frequency 2 rated value |
60 Hz |
| relative negative tolerance of the control supply voltage frequency |
-10 % |
| relative positive tolerance of the control supply voltage frequency |
10 % |
| control supply voltage 1 at AC |
|
| ● at 50 Hz rated value |
24 V |
| ● at 60 Hz rated value |
24 V |
| relative negative tolerance of the control supply voltage at AC at 50 Hz |
-20 % |
| relative positive tolerance of the control supply voltage at AC at 50 Hz |
20 % |
| relative negative tolerance of the control supply voltage at AC at 60 Hz |
-20 % |
| relative positive tolerance of the control supply voltage at AC at 60 Hz |
20 % |
| control supply voltage 1 at DC rated value |
24 V |
| relative negative tolerance of the control supply voltage at DC |
-20 % |
| relative positive tolerance of the control supply voltage at DC |
20 % |
| display version for fault signal |
red |
| Mechanical data |
|
| size of engine control device |
S00 |
| width |
45 mm |
| height |
95 mm |
| depth |
150 mm |
| fastening method |
screw and snap-on mounting |
| mounting position |
With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° tiltable to the front and back |
| required spacing with side-by-side mounting |
|
| ● upwards |
60 mm |
| ● at the side |
15 mm |
| ● downwards |
40 mm |
| wire length maximum |
300 m |
| number of poles for main current circuit |
3 |
| Connections/ Terminals |
|
| type of electrical connection |
|
| ● for main current circuit |
screw-type terminals |
| ● for auxiliary and control circuit |
screw-type terminals |
| number of NC contacts for auxiliary contacts |
0 |
| number of NO contacts for auxiliary contacts |
1 |
| number of CO contacts for auxiliary contacts |
0 |
| type of connectable conductor cross-sections for main contacts for box terminal using the front clamping point |
|
| ● solid |
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
| ● finely stranded with core end processing |
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²) |
| type of connectable conductor cross-sections for AWG cables for main contacts for box terminal |
|
| ● using the front clamping point |
2x (16 ... 10) |
| type of connectable conductor cross-sections for auxiliary contacts |
|
| ● solid |
2x (0.25 ... 2.5 mm²) |
| ● finely stranded with core end processing |
2x (0.25 ... 1.5 mm²) |
| type of connectable conductor cross-sections for AWG cables |
|
| ● for auxiliary contacts |
2x (20 ... 14) |
| ● for auxiliary contacts finely stranded with core end processing |
2x (20 ... 16) |
| Ambient conditions |
|
| installation altitude at height above sea level |
5 000 m |
| environmental category |
|
| ● during transport according to IEC 60721 |
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
| ● during storage according to IEC 60721 |
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4 |
| ● during operation according to IEC 60721 |
3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ambient temperature |
|
| ● during operation |
-25 ... +60 °C |
| ● during storage |
-40 ... +80 °C |
| derating temperature |
40 °C |
| protection class IP on the front according to IEC 60529 |
IP20 |
| touch protection on the front according to IEC 60529 |
finger-safe, for vertical contact from the front |
| UL/CSA ratings |
|
| yielded mechanical performance [hp] for 3-phase AC motor |
|
| ● at 220/230 V |
|
| — at standard circuit at 50 °C rated value |
3 hp |
| ● at 460/480 V |
|
| — at standard circuit at 50 °C rated value |
10 hp |
| contact rating of auxiliary contacts according to UL |
B300 / R300 |
| Approvals Certificates |
|
| Environmental Product Declaration |
|
| ● global warming potential [CO2 eq] / during manufacturing |
11.1 kg |
| ● global warming potential [CO2 eq] / during sales |
0.109 kg |
| ● global warming potential [CO2 eq] / during operation |
54.3 kg |
| ● global warming potential [CO2 eq] / after end of life |
-1.64 kg |
| ● global warming potential [CO2 eq] / total |
63.9 kg |