SIEMENS 6ES7155-6AA01-0BN0

  • SIEMENS | PLC Controls | Interface Modules / Power-On Units

  • EICHLER-art.no.: K1112248
  • EAN: 4047623408154

Product description

SIMATIC ET 200SP, PROFINET BUNDLE IM, IM 155-6PN ST, MAX. 32 I/O MODULES AND 16 ET 200AL MODULES, SINGLE HOT SWAP, BUNDLE CONSISTS OF: INTERFACE MODULE (6ES7155-6AU01-0BN0), SERVER MODULE (6ES7193-6PA00-0AA0), BUSADAPTER BA 2XRJ45 (6ES7193-6AR00-0AA0)

Services for SIEMENS 6ES7155-6AA01-0BN0

Repair

2-5 days

from 329,12 €

to 503,36 €

Replacement

Used

New

1-3 days

10+ Pcs.

290,40 €

290,40 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: EAR99H
Net weight 0.235
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4047623408154
UPC /
Static lot number 85176200
List indicator ST76
Product group X0FS
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20170426
Product classifications Version Classification
eClass 4 /
eClass 5.1 27-24-26-08
eClass 6.0 27-24-26-08
ETIM 3 /
ETIM 4 /
ETIM 5 EC001604

Attribute Value
General information
Product type designation IM155-6PN ST, including BusAdapter BA 2x RJ45
HW functional status From FS03
Firmware version V4.2
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping) Yes; Single hot swapping
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14
● STEP 7 configurable/integrated from version V5.5 SP4
● PROFINET from GSD version/GSD revision GSDML V2.35
Configuration control
via dataset Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Short-circuit protection Yes
Mains buffering
● Mains/voltage failure stored energy time 10 ms
Input current
Current consumption (rated value) 450 mA
Current consumption, max. 550 mA
Inrush current, max. 3.7 A
I²t 0.09 A²·s
Power loss
Power loss, typ. 1.9 W
Address area
Address space per module
● Address space per module, max. 256 byte; For input and output data respectively
Address space per station
● Address space per station, max. 512 byte
Hardware configuration
Rack
● Quantity of operable ET 200SP modules, max. 32
● Quantity of operable ET 200AL modules, max. 16
Submodules
● Number of submodules per station, max. 256
Interfaces
Transmission procedure 100BASE-TX
Number of PROFINET interfaces 1; 2 ports (switch)
1. Interface
Interface types
● RJ 45 (Ethernet) Yes; with BusAdapter
● Number of ports 2; with BusAdapter
● integrated switch Yes
● BusAdapter (PROFINET) Yes; BA 2x RJ45, BA 2x FC, BA 2x M12
Protocols
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; PROFINET MRP client
PROFINET IO Device
Services
— IRT Yes; 250 µs to 4 ms in 125 µs frame
— Dynamic Frame Packing (DFP) No
— PROFIenergy Yes
— Prioritized startup Yes
— Shared device Yes
— Number of IO Controllers with shared device, max. 2
Interface types
RJ 45 (Ethernet)
● Transmission procedure PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
Protocols
Supports protocol for PROFINET IO Yes
PROFIsafe Yes
PROFIBUS No
EtherNet/IP No
Modbus TCP No
Redundancy mode
● PROFINET system redundancy (S2) No
● PROFINET system redundancy (R1) No
Media redundancy
— MRP Yes
— MRPD No
Open IE communication
● TCP/IP Yes
● SNMP Yes
● LLDP Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Connection display LINK TX/RX Yes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronics No
between PROFINET and all other circuits Yes; 1500 V AC (type test)
between supply and all other circuits No
Permissible potential difference
between different circuits Safety extra low voltage SELV
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Network loading class 3
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 105 kg
— global warming potential, (during production) [CO2 eq] 13.7 kg
— global warming potential, (during operation) [CO2 eq] 91.9 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.617 kg
Security
PROFINET Security Class 1
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; No condensation
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; No condensation
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Connection method
ET-Connection
● via BU/BA Send Yes; + 16 ET 200AL modules
Dimensions
Width 50 mm
Height 117 mm
Depth 74 mm
Weights
Weight, approx. 147 g; without BusAdapter

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Quality & warranty

Outstanding service quality with every handle

Two Eichler technicians high-five each other after a successful repair

Your shopping basket

Loading shopping basket