| General information |
|
| Product type designation |
IM 153-1 DP ST |
| Vendor identification (VendorID) |
801Dh |
| Supply voltage |
|
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| external protection for power supply lines (recommendation) |
not necessary |
| Mains buffering |
|
| ● Mains/voltage failure stored energy time |
5 ms |
| Input current |
|
| Current consumption, max. |
350 mA; At 24 V DC |
| Inrush current, typ. |
2.5 A |
| I²t |
0.1 A²·s |
| Output voltage |
|
| Rated value (DC) |
5 V |
| Output current |
|
| for backplane bus (5 V DC), max. |
1 A |
| Power loss |
|
| Power loss, typ. |
3 W |
| Address area |
|
| Addressing volume |
|
| ● Inputs |
128 byte |
| ● Outputs |
128 byte |
| Hardware configuration |
|
| number of modules per DP device interface, max. |
8 |
| Interfaces |
|
| Transmission procedure |
RS 485 |
| Transmission rate, max. |
12 Mbit/s |
| 1. Interface |
|
| automatic detection of transmission rate |
Yes |
| Interface types |
|
| ● Output current of the interface, max. |
90 mA |
| ● Design of the connection |
9-pin sub D socket |
| PROFIBUS DP device |
|
| ● GSD file |
(for DPV1) SIEM801D.GSD; SI01801D.GSG |
| ● automatic baud rate search |
Yes |
| Protocols |
|
| Bus protocol/transmission protocol |
PROFIBUS DP to EN 50170 |
| Protocols (Ethernet) |
|
| ● TCP/IP |
No |
| PROFIBUS DP |
|
| ● Number of node addresses, max. |
1 to 125 permitted |
| Services |
|
| — SYNC capability |
Yes |
| — FREEZE capability |
Yes |
| — Direct data exchange (slave-to-slave communication) |
Yes; Sender |
| Potential separation |
|
| Potential separation exists |
Yes |
| Isolation |
|
| Isolation tested with |
Isolation voltage 500 V |
| Degree and class of protection |
|
| IP degree of protection |
IP20 |
| Ambient conditions |
|
| Ambient temperature during operation |
|
| ● min. |
0 °C |
| ● max. |
60 °C |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
40 °C |
| Altitude during operation relating to sea level |
|
| ● Installation altitude above sea level, max. |
3 000 m |
| Configuration |
|
| Configuration software |
|
| ● STEP 7 |
STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
| Dimensions |
|
| Width |
40 mm |
| Height |
125 mm |
| Depth |
117 mm |
| Weights |
|
| Weight, approx. |
360 g |