SIMATIC S7-300, DIGITAL MODULE SM 327, ISOLATED, 8DI AND 8DX, 24 V DC, 0.5 A 1X 20-POLE; 8DX BY INDIVIDUAL CHANNELS CAN BE PARAMETERIZED AS DI OR DO

Services for SIEMENS 6ES7327-1BH00-0AB0

Repair

2-5 days

from 537,44 €

to 821,96 €

Replacement

Used

3-5 days

1 Pcs.

474,84 €

451,10 €

451,10 € *

Please enter an offer recipient here.


New

Delivery information
Export identifier AL: N ECCN: EAR99H
Net weight 0.247
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4025515070832
UPC 662643172614
Static lot number 85389091
List indicator ST73
Product group 4561
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20080331
Product classifications Version Classification
eClass 4 27-24-03-04
eClass 5.1 27-24-22-04
eClass 6.0 27-24-22-04
ETIM 3 /
ETIM 4 EC001419
ETIM 5 EC001419

Attribute Value
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 20 mA
from backplane bus 5 V DC, max. 60 mA
Power loss
Power loss, typ. 3 W
Digital inputs
Number of digital inputs 8; 8 hard-wired, 8 others individually parameterizable
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 60 °C, max. 16
vertical installation
— up to 40 °C, max. 16
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal "0" -30 to +5 V
● for signal "1" +15 to +30 V
Input current
● for signal "1", typ. 6 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", min. 1.2 ms
— at "0" to "1", max. 4.8 ms
— at "1" to "0", min. 1.2 ms
— at "1" to "0", max. 4.8 ms
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Digital outputs
Number of digital outputs 8; can also be parameterized individually as DI
Short-circuit protection Yes
● Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-54 V)
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "1", min. L+ (-1.5 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, min. 5 mA
● for signal "1" permissible range, max. 0.6 A
● for signal "0" residual current, max. 0.5 mA
Output delay with resistive load
● "0" to "1", max. 350 µs
● "1" to "0", max. 500 µs
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes; only outputs of the same group
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● with inductive load (acc. to IEC 60947-5-1, DC13), max. 0.5 Hz
● on lamp load, max. 10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A
— up to 60 °C, max. 3 A
vertical installation
— up to 40 °C, max. 2 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Interrupts/diagnostics/status information
Alarms No
Diagnostics function No
Diagnostics indication LED
● Status indicator digital input (green) Yes
● Status indicator digital output (green) Yes
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels and backplane bus Yes; Optocoupler
Potential separation digital outputs
● between the channels No
● between the channels and backplane bus Yes; Optocoupler
Isolation
Isolation tested with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 200 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket