SIEMENS 6ES7136-6RA00-0BF0

  • EICHLER-art.no.: K0370490
  • EAN: 4047623402596
  • UPC: 887621782665

Product description

SIMATIC DP, Electronics module f. ET200SP, F-RQ 1x 24 V DC/24..230VAC/5A ST, 20 mm overall width, 1 relay output (2 NO) Summation output current 5 A, load voltage 24 V DC and 24.. 230 V AC, Can be used up to PL E (ISO 13849-1: 2008)/ SIL 3 (IEC 61508: 2010) if control takes place by (e.g. 6ES7136-6DB00-0CA0) F-DQ

Services for SIEMENS 6ES7136-6RA00-0BF0

Repair

2-5 days

from 108,46 €

to 165,88 €

Replacement

Used

New

1-3 days

10+ Pcs.

87,00 €

82,65 €

82,65 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: N
Net weight 0.067
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4047623402596
UPC 887621782665
Static lot number 85389091
List indicator ST76
Product group 4527
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20140331
Product classifications Version Classification
eClass 4 /
eClass 5.1 27-24-26-04
eClass 6.0 27-24-26-04
ETIM 3 /
ETIM 4 EC001599
ETIM 5 EC001599

Attribute Value
General information
Product type designation F-RQ 24 ... 48VDC/24 ... 230VAC/5A ST
usable BaseUnits BU type F0
Color code for module-specific color-coded label CC42
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13
● STEP 7 configurable/integrated from version V5.5 SP4 and higher
● PROFINET from GSD version/GSD revision V2.31
Supply voltage
Rated value (DC) 24 V; Coil voltage
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
power supply according to NEC Class 2 required No
Power
Power consumption from the backplane bus 100 mW
Power loss
Power loss, typ. 1 W
Address area
Address space per module
● Inputs 1 byte
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element type C
Digital outputs
Type of digital output Relays
Number of digital outputs 1
Limitation of inductive shutdown voltage to No
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 5 A
● on lamp load, max. 25 W
Switching frequency
● with resistive load, max. 2 Hz
● with inductive load, max. 0.1 Hz; See data in manual
● with inductive load (acc. to IEC 60947-5-1, DC13), max. 0.1 Hz
● with inductive load (acc. to IEC 60947-5-1, AC15), max. 2 Hz
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 5 A; note derating data in the manual
— up to 50 °C, max. 4 A; note derating data in the manual
— up to 60 °C, max. 3 A; note derating data in the manual
vertical installation
— up to 50 °C, max. 3 A; note derating data in the manual
Relay outputs
● Number of relay outputs 1; 2 NO contacts
● Rated supply voltage of relay coil L+ (DC) 24 V
● Current consumption of relays (coil current of all relays), max. 70 mA
● external protection for relay outputs yes; 6 A, see data in manual
● Relay approved acc. to UL 508 Yes; Pilot Duty B300, R300
Switching capacity of contacts
— with inductive load, max. see additional description in the manual
— with resistive load, max. see additional description in the manual
— Thermal continuous current, max. 5 A
— Switching current, min. 1 mA
— Switching current after exceeding 300 mA, min. 10 mA
— Switching current after exceeding 300 mA, max. 5 A
— Rated switching voltage (DC) 24 V
— Rated switching voltage (AC) 230 V
Cable length
● shielded, max. 500 m; for load contacts
● unshielded, max. 300 m; for load contacts
● Control cable (input), max. 10 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes; green/red DIAG LED
● Channel status display Yes; green LED
Potential separation
Potential separation channels
● between the channels Yes; for SELV / PELV only
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes
Permissible potential difference
between channels and backplane bus/supply voltage 250 V AC (reinforced insulation)
Isolation
Isolation tested with 2 545 V DC/2 s (routine test)
Overvoltage category III (according to IEC/EN 61131-2:2007 and EN 298:2022), II (according to IEC 61131-2:2017 and IEC 61010-2-201)
tested with
● between channels and backplane bus/supply voltage DC 2 545 V 2 s (routine test), impulse voltage test DC 7 200 V / 5 positive and 5 negative pulses (type test)
● between backplane bus and supply voltage 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Suitable for safety functions Yes
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 52 kg
— global warming potential, (during production) [CO2 eq] 6.8 kg
— global warming potential, (during operation) [CO2 eq] 45.8 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.628 kg
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1 PLe
● Category according to ISO 13849-1 4
● SIL acc. to IEC 61508 SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with SIL2 < 1.00E-04, function test 1x per year
— Low demand mode: PFDavg in accordance with SIL3 < 1.00E-05, function test 1x per month
— High demand/continuous mode: PFH in accordance with SIL2 < 1.00E-08 1/h, function test 1x per year
— High demand/continuous mode: PFH in accordance with SIL3 < 6.00E-09 1/h, function test 1x per month
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C
● vertical installation, max. 50 °C
Dimensions
Width 20 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 56 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket