SIEMENS 6ES7331-7KB02-0AB0

  • EICHLER-art.no.: K0118573
  • EAN: 4025515066781
  • UPC: 662643177299

Product description

SIMATIC S7-300, ANALOG INPUT SM 331, ISOLATED, 2 AI, RESOLUTION 9/12/14 BITS, U/I/THERMOCOUPLE/RESISTOR, ALARM, DIAGNOSTICS, 1X 20-POLE, REMOVING/INSERTING WITH ACTIVE BACKPLANE BUS

Services for SIEMENS 6ES7331-7KB02-0AB0

Repair

2-5 days

from 267,42 €

to 481,36 €

per pc. 159,00 €

Replacement

Used

3-5 days

10+ Pcs.

326,71 €

245,03 €

per pc. 159,00 €

245,03 € *

Please enter an offer recipient here.


New

1-3 days

4 Pcs.

363,00 €

272,25 €

272,25 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: EAR99H
Net weight 0.249
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status EOP: 2025-10-01
EAN 4025515066781
UPC 662643177299
Static lot number 85389091
List indicator ST73
Product group 4561
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20080331
Product classifications Version Classification
eClass 4 27-24-03-05
eClass 5.1 27-24-22-01
eClass 6.0 27-24-22-01
ETIM 3 /
ETIM 4 EC001420
ETIM 5 EC001420

Attribute Value
General information
Product function
● Isochronous mode No
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 30 mA
from backplane bus 5 V DC, max. 50 mA
Power loss
Power loss, typ. 1 W
Analog inputs
Number of analog inputs 2
● For resistance measurement 1
permissible input voltage for voltage input (destruction limit), max. 20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)
permissible input current for current input (destruction limit), max. 40 mA
Constant measurement current for resistance-type transmitter, typ. 1.67 mA
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V No
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 100 kΩ
● 1 V to 10 V No
● -1 V to +1 V Yes
— Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V Yes
— Input resistance (-2.5 V to +2.5 V) 100 kΩ
● -250 mV to +250 mV Yes
— Input resistance (-250 mV to +250 mV) 10 MΩ
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV No
● -500 mV to +500 mV Yes
— Input resistance (-500 mV to +500 mV) 10 MΩ
● -80 mV to +80 mV Yes
— Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 25 Ω
● -10 mA to +10 mA Yes
— Input resistance (-10 mA to +10 mA) 25 Ω
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 25 Ω
● -3.2 mA to +3.2 mA Yes
— Input resistance (-3.2 mA to +3.2 mA) 25 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 25 Ω
Input ranges (rated values), thermocouples
● type B No
● Type E Yes
— Input resistance (Type E) 10 MΩ
● Type J Yes
— Input resistance (type J) 10 MΩ
● Type K Yes
— Input resistance (Type K) 10 MΩ
● Type L No
● Type N Yes
— Input resistance (Type N) 10 MΩ
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Ni 100 Yes
— Input resistance (Ni 100) 10 MΩ; Standard
● Ni 1000 No
● LG-Ni 1000 No
● Ni 120 No
● Ni 200 No
● Ni 500 No
● Pt 100 Yes
— Input resistance (Pt 100) 10 kΩ; Standard
● Pt 1000 No
● Pt 200 No
● Pt 500 No
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
— Input resistance (0 to 150 ohms) 10 MΩ
● 0 to 300 ohms Yes
— Input resistance (0 to 300 ohms) 10 MΩ
● 0 to 600 ohms Yes
— Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 6000 ohms No
Thermocouple (TC)
Temperature compensation
— Parameterizable Yes
— internal temperature compensation Yes
— external temperature compensation with compensations socket Yes
— for definable comparison point temperature Yes
Characteristic linearization
● Parameterizable Yes
— for thermocouples Type E, J, K, L, N
— for resistance thermometer Pt100 (standard, climatic range), Ni100 (standard, climatic range)
Cable length
● shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 15 bit; Unipolar: 9/12/12/14 bit; bipolar: 9 bit + sign/12 bit + sign/12 bit + sign/14 bit + sign
● Integration time, parameterizable Yes; 2,5 / 16,67 / 20 / 100 ms
● Basic conversion time (ms) 3 / 17 / 22 / 102 ms
● Interference voltage suppression for interference frequency f1 in Hz 400 / 60 / 50 / 10 Hz
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 1 %; ±1% (80 mV); ±0.6% (250 mV to 1 000 mV); ±0.8% (2.5 V to 10 V)
● Current, relative to input range, (+/-) 0.7 %; From 3.2 to 20 mA
● Resistance, relative to input range, (+/-) 0.7 %; 150, 300, 600 Ohm
● Resistance thermometer, relative to input range, (+/-) 0.7 %; ±0.7 % (Pt100/ Ni100); ±0.8 % (Pt100 climate)
● Thermocouple, relative to input range, (+/-) 1.1 %; Type E, J, K, L, N
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.6 %; ±0.6% (80 mV, 2.5 V to 10 V); ±0.4% (250 mV to 1 000 mV)
● Current, relative to input range, (+/-) 0.5 %; 3.2 to 20 mA
● Resistance, relative to input range, (+/-) 0.5 %; 150, 300, 600 Ohm
● Resistance thermometer, relative to input range, (+/-) 0.6 %; ±0.5% (Pt100/ Ni100), ±0.6% (Pt100 climate)
● Thermocouple, relative to input range, (+/-) 0.7 %; Type E, N, J, K, L
Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; Parameterizable, channel 0
Diagnoses
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes; Not for 2-wire transmitters
Isolation
Isolation tested with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 250 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket