| General information |
| Product type designation AI 8xRTD/TC 2-wire HF |
| HW functional status From FS05 |
| Firmware version V2.1 |
| ● FW update possible Yes |
| usable BaseUnits BU type A0, A1 |
| Color code for module-specific color-coded label CC00 |
| Product function |
| ● I&M data Yes; I&M0 to I&M3 |
| ● Isochronous mode No |
| ● Measuring range scalable Yes |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated from version V16, V17 / V18 |
| ● STEP 7 configurable/integrated from version V5.5 SP3 / V5.5 SP4 |
| ● PCS 7 configurable/integrated from version V8.1 SP1 |
| ● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher |
| ● PROFINET from GSD version/GSD revision GSDML V2.35 |
| Operating mode |
| ● Oversampling No |
| ● MSI No |
| CiR - Configuration in RUN |
| Reparameterization possible in RUN Yes |
| Calibration possible in RUN Yes |
| Supply voltage |
| Rated value (DC) 24 V |
| permissible range, lower limit (DC) 19.2 V |
| permissible range, upper limit (DC) 28.8 V |
| Reverse polarity protection Yes |
| Input current |
| Current consumption, max. 35 mA |
| Power loss |
| Power loss, typ. 0.75 W |
| Address area |
| Address space per module |
| ● Address space per module, max. 16 byte; + 1 byte for QI information |
| Hardware configuration |
| Automatic encoding |
| ● Mechanical coding element Yes |
| ● Type of mechanical coding element Type A |
| Selection of BaseUnit for connection variants |
| ● 2-wire connection BU type A0, A1 |
| Analog inputs |
| Number of analog inputs 8 |
| permissible input voltage for voltage input (destruction limit), max. 30 V |
| Constant measurement current for resistance-type transmitter, typ. 2 mA |
| Cycle time (all channels), min. Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels) |
| Technical unit for temperature measurement adjustable Yes; °C/°F/K |
| Input ranges (rated values), voltages |
| ● -1 V to +1 V Yes; 16 bit incl. sign |
| — Input resistance (-1 V to +1 V) 1 MΩ |
| ● -250 mV to +250 mV Yes; 16 bit incl. sign |
| — Input resistance (-250 mV to +250 mV) 1 MΩ |
| ● -50 mV to +50 mV Yes; 16 bit incl. sign |
| — Input resistance (-50 mV to +50 mV) 1 MΩ |
| ● -80 mV to +80 mV Yes; 16 bit incl. sign |
| — Input resistance (-80 mV to +80 mV) 1 MΩ |
| Input ranges (rated values), thermocouples |
| ● type B Yes; 16 bit incl. sign |
| — Input resistance (Type B) 1 MΩ |
| ● type C Yes; 16 bit incl. sign |
| — Input resistance (Type C) 1 MΩ |
| ● Type E Yes; 16 bit incl. sign |
| — Input resistance (Type E) 1 MΩ |
| ● Type J Yes; 16 bit incl. sign |
| — Input resistance (type J) 1 MΩ |
| ● Type K Yes; 16 bit incl. sign |
| — Input resistance (Type K) 1 MΩ |
| ● Type L Yes; 16 bit incl. sign |
| — Input resistance (Type L) 1 MΩ |
| ● Type N Yes; 16 bit incl. sign |
| — Input resistance (Type N) 1 MΩ |
| ● Type R Yes; 16 bit incl. sign |
| — Input resistance (Type R) 1 MΩ |
| ● Type S Yes; 16 bit incl. sign |
| — Input resistance (Type S) 1 MΩ |
| ● Type T Yes; 16 bit incl. sign |
| — Input resistance (Type T) 1 MΩ |
| ● Type U Yes; 16 bit incl. sign |
| — Input resistance (Type U) 1 MΩ |
| ● Type TXK/TXK(L) to GOST Yes; 16 bit incl. sign |
| — Input resistance (Type TXK/TXK(L) to GOST) 1 MΩ |
| Input ranges (rated values), resistance thermometer |
| ● Ni 100 Yes; 16 bit incl. sign |
| — Input resistance (Ni 100) 1 MΩ |
| ● Ni 1000 Yes; 16 bit incl. sign |
| — Input resistance (Ni 1000) 1 MΩ |
| ● LG-Ni 1000 Yes; 16 bit incl. sign |
| — Input resistance (LG-Ni 1000) 1 MΩ |
| ● Ni 120 Yes; 16 bit incl. sign |
| — Input resistance (Ni 120) 1 MΩ |
| ● Ni 200 Yes; 16 bit incl. sign |
| — Input resistance (Ni 200) 1 MΩ |
| ● Ni 500 Yes; 16 bit incl. sign |
| — Input resistance (Ni 500) 1 MΩ |
| ● Pt 100 Yes; 16 bit incl. sign |
| — Input resistance (Pt 100) 1 MΩ |
| ● Pt 1000 Yes; 16 bit incl. sign |
| — Input resistance (Pt 1000) 1 MΩ |
| ● Pt 200 Yes; 16 bit incl. sign |
| — Input resistance (Pt 200) 1 MΩ |
| ● Pt 500 Yes; 16 bit incl. sign |
| — Input resistance (Pt 500) 1 MΩ |
| Input ranges (rated values), resistors |
| ● 0 to 150 ohms Yes; 15 bit |
| — Input resistance (0 to 150 ohms) 1 MΩ |
| ● 0 to 300 ohms Yes; 15 bit |
| — Input resistance (0 to 300 ohms) 1 MΩ |
| ● 0 to 600 ohms Yes; 15 bit |
| — Input resistance (0 to 600 ohms) 1 MΩ |
| ● 0 to 3000 ohms Yes; 15 bit |
| — Input resistance (0 to 3000 ohms) 1 MΩ |
| ● 0 to 6000 ohms Yes; 15 bit |
| — Input resistance (0 to 6000 ohms) 1 MΩ |
| ● PTC Yes; 15 bit |
| — Input resistance (PTC) 1 MΩ |
| Thermocouple (TC) |
| Temperature compensation |
| — Parameterizable Yes |
| — Reference channel of the module Yes |
| — internal comparison point Yes; with BaseUnit type A1 |
| — Reference channel of the group Yes |
| — Number of reference channel groups 4; Group 0 to 3 |
| — fixed reference temperature Yes |
| Cable length |
| ● shielded, max. 200 m; 50 m with thermocouples |
| Analog value generation for the inputs |
| Measurement principle integrating (Sigma-Delta) |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. 16 bit |
| ● Integration time, parameterizable Yes |
| ● Basic conversion time, including integration time (ms) |
| — additional processing time for wire-break check 2 ms; In the ranges resistance thermometers, resistors and thermocouples |
| ● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 Hz |
| ● Conversion time (per channel) 180 / 60 / 50 / (67.5 / 22.5 / 18.75) ms |
| Smoothing of measured values |
| ● Number of smoothing levels 4; None; 4/8/16 times |
| ● parameterizable Yes |
| Encoder |
| Connection of signal encoders |
| ● for voltage measurement Yes |
| ● for resistance measurement with two-wire connection Yes |
| ● for resistance measurement with three-wire connection No |
| ● for resistance measurement with four-wire connection No |
| Errors/accuracies |
| Linearity error (relative to input range), (+/-) 0.01 %; ±0.1 % for resistance thermometers and resistance |
| Temperature error (relative to input range), (+/-) 0.0009 %/K; ±0.005 % / K at thermocouple |
| Crosstalk between the inputs, min. -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 % |
| Operational error limit in overall temperature range |
| ● Voltage, relative to input range, (+/-) 0.1 % |
| ● Resistance, relative to input range, (+/-) 0.1 % |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to input range, (+/-) 0.05 % |
| ● Resistance, relative to input range, (+/-) 0.05 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
| ● Series mode interference (peak value of interference < rated value of input range), min. 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB |
| ● Common mode voltage, max. 10 V |
| ● Common mode interference, min. 90 dB |
| Interrupts/diagnostics/status information |
| Alarms |
| ● Diagnostic alarm Yes |
| ● Limit value alarm Yes; two upper and two lower limit values in each case |
| Diagnoses |
| ● Monitoring the supply voltage Yes |
| ● Wire break Yes; channel by channel |
| ● Group error Yes |
| ● Overflow/Underflow Yes; channel by channel |
| Diagnostics indication LED |
| ● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED |
| ● Channel status display Yes; green LED |
| ● for channel diagnostics Yes; red LED |
| ● for module diagnostics Yes; green/red DIAG LED |
| Potential separation |
| Potential separation channels |
| ● between the channels No |
| ● between the channels and backplane bus Yes |
| ● between the channels and the power supply of the electronics Yes |
| Permissible potential difference |
| between the inputs (UCM) 10 V DC |
| Isolation |
| Isolation tested with 707 V DC (type test) |
| Standards, approvals, certificates |
| Ecological footprint |
| ● environmental product declaration Yes |
| Global warming potential |
| — global warming potential, (total) [CO2 eq] 9.32 kg |
| — global warming potential, (during production) [CO2 eq] 4.97 kg |
| — global warming potential, (during operation) [CO2 eq] 4.79 kg |
| — global warming potential, (after end of life cycle) [CO2 eq] -0.449 kg |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. -30 °C |
| ● horizontal installation, max. 60 °C |
| ● vertical installation, min. -30 °C |
| ● vertical installation, max. 50 °C |
| Altitude during operation relating to sea level |
| ● Installation altitude above sea level, max. 2 000 m; On request: Installation altitudes greater than 2 000 m |
| Absolute humidity |
| ● dew point, min. -60 °C; suitable for dry room applications |
| Dimensions |
| Width 15 mm |
| Height 73 mm |
| Depth 58 mm |