SIEMENS 6ES7134-6JF00-0CA1

  • EICHLER-art.no.: K0370485
  • EAN: 4047623403388
  • UPC: 887621782672

Product description

SIMATIC ET 200SP, ANALOG INPUT MODULE, AI 8XRTD/TC 2-WIRE HIGH FEATURE FITS TO BU-TYPE A0, A1, COLOR CODE CC00, CHANNEL DIAGNOSIS, 16BIT, +/-0,1%

Services for SIEMENS 6ES7134-6JF00-0CA1

Repair

2-5 days

from 300,30 €

to 459,28 €

Replacement

Used

New

1-3 days

10+ Pcs.

257,25 €

244,39 €

244,39 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: EAR99H
Net weight 0.039
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4047623403388
UPC 887621782672
Static lot number 85389091
List indicator ST76
Product group 4520
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20140225
Product classifications Version Classification
eClass 4 /
eClass 5.1 27-24-26-01
eClass 6.0 27-24-26-01
ETIM 3 /
ETIM 4 EC001596
ETIM 5 EC001596

Attribute Value
General information
Product type designation AI 8xRTD/TC 2-wire HF
HW functional status From FS05
Firmware version V2.1
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color-coded label CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Measuring range scalable Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V16, V17 / V18
● STEP 7 configurable/integrated from version V5.5 SP3 / V5.5 SP4
● PCS 7 configurable/integrated from version V8.1 SP1
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.35
Operating mode
● Oversampling No
● MSI No
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 35 mA
Power loss
Power loss, typ. 0.75 W
Address area
Address space per module
● Address space per module, max. 16 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 2-wire connection BU type A0, A1
Analog inputs
Number of analog inputs 8
permissible input voltage for voltage input (destruction limit), max. 30 V
Constant measurement current for resistance-type transmitter, typ. 2 mA
Cycle time (all channels), min. Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Input ranges (rated values), voltages
● -1 V to +1 V Yes; 16 bit incl. sign
— Input resistance (-1 V to +1 V) 1 MΩ
● -250 mV to +250 mV Yes; 16 bit incl. sign
— Input resistance (-250 mV to +250 mV) 1 MΩ
● -50 mV to +50 mV Yes; 16 bit incl. sign
— Input resistance (-50 mV to +50 mV) 1 MΩ
● -80 mV to +80 mV Yes; 16 bit incl. sign
— Input resistance (-80 mV to +80 mV) 1 MΩ
Input ranges (rated values), thermocouples
● type B Yes; 16 bit incl. sign
— Input resistance (Type B) 1 MΩ
● type C Yes; 16 bit incl. sign
— Input resistance (Type C) 1 MΩ
● Type E Yes; 16 bit incl. sign
— Input resistance (Type E) 1 MΩ
● Type J Yes; 16 bit incl. sign
— Input resistance (type J) 1 MΩ
● Type K Yes; 16 bit incl. sign
— Input resistance (Type K) 1 MΩ
● Type L Yes; 16 bit incl. sign
— Input resistance (Type L) 1 MΩ
● Type N Yes; 16 bit incl. sign
— Input resistance (Type N) 1 MΩ
● Type R Yes; 16 bit incl. sign
— Input resistance (Type R) 1 MΩ
● Type S Yes; 16 bit incl. sign
— Input resistance (Type S) 1 MΩ
● Type T Yes; 16 bit incl. sign
— Input resistance (Type T) 1 MΩ
● Type U Yes; 16 bit incl. sign
— Input resistance (Type U) 1 MΩ
● Type TXK/TXK(L) to GOST Yes; 16 bit incl. sign
— Input resistance (Type TXK/TXK(L) to GOST) 1 MΩ
Input ranges (rated values), resistance thermometer
● Ni 100 Yes; 16 bit incl. sign
— Input resistance (Ni 100) 1 MΩ
● Ni 1000 Yes; 16 bit incl. sign
— Input resistance (Ni 1000) 1 MΩ
● LG-Ni 1000 Yes; 16 bit incl. sign
— Input resistance (LG-Ni 1000) 1 MΩ
● Ni 120 Yes; 16 bit incl. sign
— Input resistance (Ni 120) 1 MΩ
● Ni 200 Yes; 16 bit incl. sign
— Input resistance (Ni 200) 1 MΩ
● Ni 500 Yes; 16 bit incl. sign
— Input resistance (Ni 500) 1 MΩ
● Pt 100 Yes; 16 bit incl. sign
— Input resistance (Pt 100) 1 MΩ
● Pt 1000 Yes; 16 bit incl. sign
— Input resistance (Pt 1000) 1 MΩ
● Pt 200 Yes; 16 bit incl. sign
— Input resistance (Pt 200) 1 MΩ
● Pt 500 Yes; 16 bit incl. sign
— Input resistance (Pt 500) 1 MΩ
Input ranges (rated values), resistors
● 0 to 150 ohms Yes; 15 bit
— Input resistance (0 to 150 ohms) 1 MΩ
● 0 to 300 ohms Yes; 15 bit
— Input resistance (0 to 300 ohms) 1 MΩ
● 0 to 600 ohms Yes; 15 bit
— Input resistance (0 to 600 ohms) 1 MΩ
● 0 to 3000 ohms Yes; 15 bit
— Input resistance (0 to 3000 ohms) 1 MΩ
● 0 to 6000 ohms Yes; 15 bit
— Input resistance (0 to 6000 ohms) 1 MΩ
● PTC Yes; 15 bit
— Input resistance (PTC) 1 MΩ
Thermocouple (TC)
Temperature compensation
— Parameterizable Yes
— Reference channel of the module Yes
— internal comparison point Yes; with BaseUnit type A1
— Reference channel of the group Yes
— Number of reference channel groups 4; Group 0 to 3
— fixed reference temperature Yes
Cable length
● shielded, max. 200 m; 50 m with thermocouples
Analog value generation for the inputs
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Basic conversion time, including integration time (ms)
— additional processing time for wire-break check 2 ms; In the ranges resistance thermometers, resistors and thermocouples
● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 Hz
● Conversion time (per channel) 180 / 60 / 50 / (67.5 / 22.5 / 18.75) ms
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times
● parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection No
● for resistance measurement with four-wire connection No
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %; ±0.1 % for resistance thermometers and resistance
Temperature error (relative to input range), (+/-) 0.0009 %/K; ±0.005 % / K at thermocouple
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.1 %
● Resistance, relative to input range, (+/-) 0.1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.05 %
● Resistance, relative to input range, (+/-) 0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB
● Common mode voltage, max. 10 V
● Common mode interference, min. 90 dB
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltage Yes
● Wire break Yes; channel by channel
● Group error Yes
● Overflow/Underflow Yes; channel by channel
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes
Permissible potential difference
between the inputs (UCM) 10 V DC
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 9.32 kg
— global warming potential, (during production) [CO2 eq] 4.97 kg
— global warming potential, (during operation) [CO2 eq] 4.79 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.449 kg
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 2 000 m; On request: Installation altitudes greater than 2 000 m
Absolute humidity
● dew point, min. -60 °C; suitable for dry room applications
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket