SIEMENS 6ES7134-6GD00-0BA1

  • EICHLER-art.no.: K0316555
  • EAN: 4025515080640
  • UPC: 040892933505

Product description

SIMATIC ET 200SP, analog input module, AI 4XI 2-/4-wire standard, suitable for BU type A0, A1, Color code CC03, Module diagnostics, 16 bit, +/-0.3%

Services for SIEMENS 6ES7134-6GD00-0BA1

Repair

2-5 days

from 157,25 €

to 240,50 €

Replacement

Used

New

1-3 days

10+ Pcs.

138,75 €

131,81 €

131,81 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: EAR99H
Net weight 0.04
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status EOP: 2018-04-25
EAN 4025515080640
UPC 040892933505
Static lot number 85389091
List indicator ST76
Product group 4B12
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20120131
Product classifications Version Classification
eClass 4 /
eClass 5.1 27-24-26-01
eClass 6.0 27-24-26-01
ETIM 3 /
ETIM 4 EC001596
ETIM 5 EC001596

Attribute Value
General information
Product type designation AI 4xI 2-/4-wire ST
Firmware version V1.1
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification plate CC03
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V11 SP2 / V13
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PCS 7 configurable/integrated from version V8.1 SP1
● PROFIBUS from GSD version/GSD revision GSD Revision 5
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSI No
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 37 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ. 0.85 W; Without encoder supply voltage
Address area
Address space per module
● Address space per module, max. 8 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Analog inputs
Number of analog inputs 4; Differential inputs
● For current measurement 4
permissible input current for current input (destruction limit), max. 50 mA
Cycle time (all channels), min. Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage in 2-wire operation
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 100 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage in 2-wire operation
Cable length
● shielded, max. 1 000 m
Analog value generation for the inputs
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 Hz
● Conversion time (per channel) 180 / 60 / 50 ms
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times
● parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement No
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB; Applies to up to ±5 V overvoltage in other channels
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode voltage, max. 10 V
● Common mode interference, min. 90 dB
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; at 4 to 20 mA
● Short-circuit Yes; 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red LED
Potential separation
Potential separation channels
● between the channels Yes; channel group-specific between 2-wire current input group and 4-wire voltage input group
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes; only for 4-wire transducer
Permissible potential difference
between the inputs (UCM) 10 V DC
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 31 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket