SIEMENS 6ES7123-1GB60-0AB0

  • EICHLER-art.no.: K0118042
  • EAN: 4025515057826

Product description

SIMATIC SC,ELECTRONIC SUBMODULE 2 AI, 4..20MA, 2 MS CONVERSION TIME P. CHANNEL FOR 4-WIRE-TRANSDUCER

Services for SIEMENS 6ES7123-1GB60-0AB0

Repair

2-5 days

from 692,91 €

to 1.059,75 €

Replacement

Used

New

1-3 days

1 Pcs.

611,39 €

580,82 €

580,82 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: ECCN:
Net weight 0.025
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status EOP: 2004-10-01
EAN 4025515057826
UPC /
Static lot number 85389091
List indicator /
Product group 4467
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: /
Product classifications Version Classification
eClass 4 /
eClass 5.1 /
eClass 6.0 /
ETIM 3 /
ETIM 4 /
ETIM 5 /

Attribute Value
General information
Usable terminal block TB 16IM-SC
Supply voltage
Rated value (DC) 24 V
Reverse polarity protection Yes
Input current
from supply voltage L+, max. 30 mA
Power loss
Power loss, typ. 0.6 W
Hardware configuration
Slots
● required slots 1; from 8
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 35 mA; 35 mA continuous, 150 mA for max. 1 s (mark to space ratio 1:20)
Input ranges
● Current Yes
Input ranges (rated values), currents
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 50 kΩ
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 50 Ω
Thermocouple (TC)
Temperature compensation
— parameterizable No
Characteristic linearization
● parameterizable No
Cable length
● shielded, max. 200 m
Analog value generation for the inputs
Measurement principle Actual value encryption
Integration and conversion time/resolution per channel
● Resolution (incl. overrange) 4 to 20 mA: 11 bit, ±20 mA: 12 bit incl. sign
● Resolution with overrange (bit including sign), max. 12 bit
● Integration time, parameterizable No
● Basic conversion time (ms) 1 ms
Smoothing of measured values
● parameterizable Yes; parameterizable in 4 stages by means of digital filtering
● Step: None Yes; 1x cycle time
● Step: low Yes; 8x cycle time
● Step: Medium Yes; 64x cycle time
● Step: High Yes; 128x cycle time
Encoder
Connection of signal encoders
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.05 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. 50 dB; At 50/60 Hz
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.1 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB; With smoothing factor k = 128
● Common mode interference (USS < 2.5 V), min. 50 dB
Interrupts/diagnostics/status information
Alarms No
Diagnostics function No
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus No
● between the channels and the power supply of the electronics No
Permissible potential difference
Between the inputs and MANA (UCM) 2 V DC / 2 Vpp AC
Dimensions
Width 10 mm
Height 64 mm
Depth 51 mm
Weights
Weight, approx. 20 g