Product description

SIPLUS S7-300 SM 331 20-pole based on 6ES7331-7KF02-0AB0 with conformal coating, -25…+70 °C, analog input isolated 8 AI, resolution 9/12/14 bits, U/I/thermocouple/resistor, alarm, diagnostics, 1x 20-pole removing/inserting with active backplane bus

Services for SIEMENS 6AG1331-7KF02-2AB0

Repair

2-5 days

from 775,86 €

to 1.140,98 €

per pc. 159,00 €

Replacement

Used

New

1-3 days

2 Pcs.

1.520,30 €

1.520,30 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: N
Net weight 0.289
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status EOP: 2025-10-01
EAN 4025515140610
UPC 662643198645
Static lot number 85389091
List indicator A&DSE/SIP ADD
Product group 4398
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20120101
Product classifications Version Classification
eClass 4 27-24-03-05
eClass 5.1 27-24-22-01
eClass 6.0 27-24-22-01
ETIM 3 /
ETIM 4 EC001420
ETIM 5 EC001420

Attribute Value
General information
based on 6ES7331-7KF02-0AB0
Product function
● Isochronous mode No
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; A power supply according to EN 50155 shall be used for railway applications
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 200 mA
from backplane bus 5 V DC, max. 50 mA
Power loss
Power loss, typ. 1 W
Analog inputs
Number of analog inputs 8
● For resistance measurement 4
permissible input voltage for voltage input (destruction limit), max. 20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)
permissible input current for current input (destruction limit), max. 40 mA
Constant measurement current for resistance-type transmitter, typ. 1.67 mA
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V No
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 100 kΩ
● 1 V to 10 V No
● -1 V to +1 V Yes
— Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V Yes
— Input resistance (-2.5 V to +2.5 V) 100 kΩ
● -250 mV to +250 mV Yes
— Input resistance (-250 mV to +250 mV) 10 MΩ
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV No
● -500 mV to +500 mV Yes
— Input resistance (-500 mV to +500 mV) 10 MΩ
● -80 mV to +80 mV Yes
— Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 25 Ω
● -10 mA to +10 mA Yes
— Input resistance (-10 mA to +10 mA) 25 Ω
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 25 Ω
● -3.2 mA to +3.2 mA Yes
— Input resistance (-3.2 mA to +3.2 mA) 25 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 25 Ω
Input ranges (rated values), thermocouples
● type B No
● type C No
● Type E Yes
— Input resistance (Type E) 10 MΩ
● Type J Yes
— Input resistance (type J) 10 MΩ
● Type K Yes
— Input resistance (Type K) 10 MΩ
● Type L No
● Type N Yes
— Input resistance (Type N) 10 MΩ
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Ni 100 Yes; Standard
— Input resistance (Ni 100) 10 MΩ
● Ni 1000 No
● LG-Ni 1000 No
● Ni 120 No
● Ni 200 No
● Ni 500 No
● Pt 100 Yes; Standard
— Input resistance (Pt 100) 10 MΩ
● Pt 1000 No
● Pt 200 No
● Pt 500 No
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
— Input resistance (0 to 150 ohms) 10 MΩ
● 0 to 300 ohms Yes
— Input resistance (0 to 300 ohms) 10 MΩ
● 0 to 600 ohms Yes
— Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 6000 ohms No
Thermocouple (TC)
Temperature compensation
— Parameterizable Yes
— internal temperature compensation Yes
— external temperature compensation with compensations socket Yes
— for definable comparison point temperature Yes
Characteristic linearization
● Parameterizable Yes
— for thermocouples Type E, J, K, L, N
— for resistance thermometer Pt100 (standard, climatic range), Ni100 (standard, climatic range)
Cable length
● shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 15 bit; Unipolar: 9/12/12/14 bit; bipolar: 9 bit + sign/12 bit + sign/12 bit + sign/14 bit + sign
● Integration time, parameterizable Yes; 2,5 / 16,67 / 20 / 100 ms
● Interference voltage suppression for interference frequency f1 in Hz 400 / 60 / 50 / 10 Hz
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 1 %; ±1% (80 mV); ±0.6% (250 mV to 1 000 mV); ±0.8% (2.5 V to 10 V) @ 0 ... +60 °C; ±1.3% (80 mV); ±0.8% (250 mV to 1 000 mV); ±1% (2.5 V to 10 V) @ -25 ... +70 °C
● Current, relative to input range, (+/-) 0.7 %; @ 0 ... +60 °C; ±0.9% @ -25 ... +70 °C; from 3.2 mA to 20 mA
● Resistance, relative to input range, (+/-) 0.7 %; @ 0 ... +60 °C; ±0.9% @ -25 ... +70 °C; 150, 300, 600 ohm
● Resistance thermometer, relative to input range, (+/-) 0.7 %; ±0.7 % (Pt100 / Ni100); ±0.8 % (Pt100 climate) @ 0 ... +60 °C; ±0.9 % (Pt100 / Ni100); ±1 % (Pt100 climate) @ -25 ... +70 °C
● Thermocouple, relative to input range, (+/-) 1.1 %; @ 0 ... +60 °C; ±1.3% @ -25 ... +70 °C; type E, J, K, L, N
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.6 %; ±0.4 % (250 mV to 1 000 mV); ±0.6 % (2.5 mV to 10 mV); ±0.7 % (80 mV)
● Current, relative to input range, (+/-) 0.5 %; 3.2 to 20 mA
● Resistance, relative to input range, (+/-) 0.5 %; 150, 300, 600 Ohm
● Resistance thermometer, relative to input range, (+/-) 0.6 %; ±0.5% (Pt100/ Ni100), ±0.6% (Pt100 climate)
● Thermocouple, relative to input range, (+/-) 0.7 %; Type E, N, J, K, L
Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Alarms
● Diagnostic alarm Yes; Parameterizable, channels 0 and 2
● Limit value alarm Yes; Parameterizable
Diagnoses
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50155 Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007 (see SIOS entry 109755985)
Ambient conditions
Ambient temperature during operation
● min. -25 °C; = Tmin
● max. 70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5 Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5 Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
— to mechanically active substances according to EN 60721-3-5 Yes; Class 5S3 incl. sand, dust; *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6 Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6 Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6 Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4 Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 * The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 250 g