| General information |
|
| Technical Product Detail Page |
https://i.siemens.com/1P6EP1333-1LB00 |
| input |
|
| type of the power supply network |
1-phase AC |
| supply voltage at AC |
Set by means of selector switch on the device |
| supply voltage |
120 V/230 V |
| input voltage 1 at AC |
93 ... 132 V |
| input voltage 2 at AC |
187 ... 264 V |
| wide range input |
No |
| overvoltage overload capability |
2.3 × Vin rated, 1.3 ms |
| buffering time for rated value of the output current in the event of power failure minimum |
20 ms |
| operating condition of the mains buffering |
at Vin = 93/187 V |
| line frequency |
50/60 Hz |
| line frequency |
47 ... 63 Hz |
| input current |
|
| ● at rated input voltage 120 V |
2.1 A |
| ● at rated input voltage 230 V |
1.15 A |
| current limitation of inrush current at 25 °C maximum |
32 A |
| duration of inrush current limiting at 25 °C |
|
| ● typical |
3 ms |
| I2t value maximum |
0.8 A²·s |
| fuse protection type |
T 3,15 A/250 V (not accessible) |
| fuse protection type in the feeder |
Recommended miniature circuit breaker: from 6 A characteristic C |
| output |
|
| voltage curve at output |
Controlled, isolated DC voltage |
| output voltage at DC rated value |
24 V |
| output voltage |
|
| ● at output 1 at DC rated value |
24 V |
|
|
| output voltage adjustable |
Yes; via potentiometer |
| adjustable output voltage |
22.8 ... 26.4 V |
| relative overall tolerance of the voltage |
3 % |
| relative control precision of the output voltage |
|
| ● on slow fluctuation of input voltage |
0.1 % |
| ● on slow fluctuation of ohm loading |
0.5 % |
| residual ripple |
|
| ● maximum |
150 mV |
| ● typical |
50 mV |
| voltage peak |
|
| ● maximum |
240 mV |
| ● typical |
150 mV |
| display version for normal operation |
Green LED for 24 V OK |
| behavior of the output voltage when switching on |
Overshoot of Vout approx. 4 % |
| response delay maximum |
1.5 s |
| voltage increase time of the output voltage |
|
| ● typical |
130 ms |
| output current |
|
| ● rated value |
5 A |
| ● rated range |
0 ... 5 A; +45 ... +60 °C: Derating 2%/K |
|
|
| supplied active power typical |
120 W |
| bridging of equipment |
Yes |
| number of parallel-switched equipment resources for increasing the power |
2 |
| efficiency |
|
| efficiency in percent |
86 % |
| power loss [W] |
|
| ● at rated output voltage for rated value of the output current typical |
17 W |
| closed-loop control |
|
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
0.3 % |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical |
2 % |
| setting time |
|
| ● load step 10 to 90% typical |
0.4 ms |
| ● load step 90 to 10% typical |
0.4 ms |
| protection and monitoring |
|
| design of the overvoltage protection |
< 33 V |
| property of the output short-circuit proof |
Yes |
| design of short-circuit protection |
Constant current characteristic |
| ● typical |
5.25 A |
| enduring short circuit current RMS value |
|
| ● typical |
8 A |
| safety |
|
| galvanic isolation between input and output |
Yes |
| galvanic isolation |
Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class |
Class I |
| leakage current |
|
| ● maximum |
3.5 mA |
| ● typical |
0.4 mA |
| protection class IP |
IP20 |
| EMC |
|
| standard |
|
| ● for emitted interference |
EN 55022 Class A |
| ● for mains harmonics limitation |
- |
| ● for interference immunity |
EN 61000-6-2 |
| standards, specifications, approvals |
|
| certificate of suitability |
|
| ● CE marking |
Yes |
| ● UL approval |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
| ● UKCA marking |
Yes |
| ● EAC approval |
Yes |
| ● NEC Class 2 |
No |
| type of certification |
|
| ● BIS |
Yes; R-41183539 |
| ● CB-certificate |
Yes |
| MTBF at 40 °C |
3 076 166 h |
| standards, specifications, approvals hazardous environments |
|
| certificate of suitability |
|
| ● IECEx |
No |
| ● ATEX |
No |
| ● ULhazloc approval |
No |
| ● FM registration |
No |
| standards, specifications, approvals marine classification |
|
| shipbuilding approval |
No |
| Marine classification association |
|
| ● American Bureau of Shipping Europe Ltd. (ABS) |
No |
| ● French marine classification society (BV) |
No |
| ● Det Norske Veritas (DNV) |
No |
| ● Lloyds Register of Shipping (LRS) |
No |
| standards, specifications, approvals Environmental Product Declaration |
|
| Environmental Product Declaration |
Yes |
| global warming potential [CO2 eq] |
|
| ● total |
474.3 kg |
| ● during manufacturing |
12.9 kg |
| ● during operation |
460.8 kg |
| ● after end of life |
0.37 kg |
| ambient conditions |
|
| ambient temperature |
|
| ● during operation |
0 ... 60 °C; with natural convection |
| ● during transport |
-40 ... +85 °C |
| ● during storage |
-40 ... +85 °C |
| environmental category according to IEC 60721 |
Climate class 3K3, 5 ... 95% no condensation |
| connection method |
|
| type of electrical connection |
screw terminal |
| ● at input |
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded |
| ● at output |
+, -: 2 screw terminals each for 0.5 ... 2.5 mm² |
| ● for auxiliary contacts |
- |
| mechanical data |
|
| width × height × depth of the enclosure |
50 × 125 × 120 mm |
| installation width × mounting height |
50 mm × 225 mm |
| required spacing |
|
| ● top |
50 mm |
| ● bottom |
50 mm |
| ● left |
0 mm |
| ● right |
0 mm |
| fastening method |
Snaps onto DIN rail EN 60715 35x7.5/15 |
| ● DIN-rail mounting |
Yes |
| ● S7 rail mounting |
No |
| ● wall mounting |
No |
| housing can be lined up |
Yes |
| net weight |
0.5 kg |