SIEMENS 6ES7633-1DF02-0AE3

  • SIEMENS | HMI | Compact Tools

  • EICHLER-art.no.: K0118928
  • EAN: 4019169021005

Product description

SIMATIC C7-633/P,KOMPLETTGERAET MIT INTEGRIERTEN KOMPONENTEN: S7-300 CPU 315, OP7, IM360 16DI, 16DO, 4AI, 4AO, 4 UI

Services for SIEMENS 6ES7633-1DF02-0AE3

Repair

1-3 days

from 1.926,06 €

to 3.466,91 €

per pc. 159,00 €

Replacement

1-3 days

10+ Pcs.

3.009,60 €

per pc. 159,00 €

3.009,60 € *

Please enter an offer recipient here.


Used

1-3 days

10+ Pcs.

3.344,00 €

per pc. 159,00 €

3.344,00 € *

Please enter an offer recipient here.


New

Delivery information
Export identifier AL: ECCN:
Net weight 2.33
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status EOP: 2017-06-30
EAN 4019169021005
UPC /
Static lot number 85371091
List indicator /
Product group 4240
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: /
Product classifications Version Classification
eClass 4 /
eClass 5.1 /
eClass 6.0 /
ETIM 3 /
ETIM 4 /
ETIM 5 /

Attribute Value
Display
Design of display LCD backlit
Line display
● Number of lines 4
● Number of characters per line 20
● Character size 8 mm
Backlighting
● MTBF backlighting (at 25 °C) 100 000 h; about 11 years
Control elements
Keyboard fonts
● Function keys
— Number of function keys 16
— Number of softkeys 4
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 30.2 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 550 mA
Current consumption, max. 1 A
Power loss
Power loss, typ. 12 W
Memory
Work memory
● integrated 48 kbyte; 16 K instructions RAM
Load memory
● expandable FEPROM Yes
● expandable FEPROM, max. 512 kbyte
● integrated RAM, max. 80 kbyte
Backup
● present Yes
● with battery Yes; all data
● without battery Yes; 4 736 byte: parameterizable for memory bits, times, counters, data
CPU processing times
for bit operations, typ. 0.3 µs
for bit operations, max. 0.6 µs
for word operations, typ. 1 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 50 µs
for timer/counter operations, typ. 12 µs
CPU-blocks
DB
● Number, max. 255; DB 0 reserved
FB
● Number, max. 192; see instruction list
FC
● Number, max. 192; see instruction list
OB
● Number, max. see instruction list
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of cyclic interrupt OBs 1; OB 35
● Number of process alarm OBs 1; OB 40
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 7; OB 80, 81, 82, 85, 87, 121, 122
Nesting depth
● per priority class 8
Counters, timers and their retentivity
S7 counter
● Number 64
Retentivity
— adjustable Yes
Counting range
— lower limit 0
— upper limit 999
S7 times
● Number 128
Retentivity
— adjustable Yes
Time range
— lower limit 10 ms
— upper limit 9 990 s
Data areas and their retentivity
Flag
● Size, max. 256 byte
● Retentivity available Yes
● of which retentive with battery 0 to 2047
● of which retentive without battery 0 to 2047
Address area
I/O address area
● Inputs 1 kbyte
● Outputs 1 kbyte
Process image
● Inputs 128 byte
● Outputs 128 byte
Hardware configuration
connectable programming devices/PCs SIMATIC PG/PC, standard PC
Number of modules per system, max. 8
Number of modules per DP slave interface, max. 32; 122 byte address space per DP station
Interface modules
● Interface module IM 360 integrated Yes
Number of DP masters
● integrated 0
● via CP 1; CP 342-5
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 4
● CP, LAN 2
Expansion modules
● Analog inputs/outputs, max. 192
● Digital inputs/outputs, max. 768
● Number of expansion modules, max. 24
Rack
● Modules per rack, max. 8
● Number of lines, max. 3
Time of day
Clock
● Hardware clock (real-time) Yes; CPU
● Software clock Yes; OP
Digital inputs
Number of digital inputs 16
Number of universal inputs 4
● usable as UI1, UI2: Digital/alarm input 24 V DC or up/down counter; UI3: Digital/alarm input 24 V DC or up/down counter or frequency/period duration counter; UI4: Digital/alarm input 24 V DC
Input voltage
● Rated value (DC) 24 V
● for signal "0" -3 to +5V
● for signal "1" +11 to +30V
Input current
● for signal "1", typ. 11.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max. 4.8 ms; typically 3 ms
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Digital outputs
Number of digital outputs 16
Short-circuit protection Yes; Clocked electronically
Limitation of inductive shutdown voltage to 48 V
Switching capacity of the outputs
● on lamp load, max. 5 W
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" minimum load current 5 mA
● for signal "0" residual current, max. 0.5 mA
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
Total current of the outputs (per group)
all mounting positions
— up to 20 °C, max. 4 A
— up to 40 °C, max. 2 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Analog inputs
Number of analog inputs 4
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 30 mA
Cycle time (all channels), typ. 2 ms
Input ranges
● Voltage Yes
● Current Yes
Input ranges (rated values), voltages
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 50 kΩ
Input ranges (rated values), currents
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 105.5 kΩ
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 16 V; ±
Cycle time (all channels) max. 4 ms; typ. 2 ms
Output ranges, voltage
● -10 V to +10 V Yes
Output ranges, current
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 2 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 0.5 kΩ
● with current outputs, inductive load, max. 1 mH
Cable length
● shielded, max. 200 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit
● Conversion time (per channel) 0.5 ms
Settling time
● for resistive load 0.1 ms
● for capacitive load 3.3 ms
● for inductive load 0.5 ms
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 2 mA
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.8 %
● Current, relative to input range, (+/-) 0.8 %
● Voltage, relative to output range, (+/-) 0.8 %
● Current, relative to output range, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.6 %
● Current, relative to input range, (+/-) 0.6 %
● Voltage, relative to output range, (+/-) 0.5 %
● Current, relative to output range, (+/-) 0.6 %
Interfaces
Number of printer interfaces 1; RS 232
MPI
● Cable length, max. 9 100 m; without repeaters 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with star hubs or OLMs)
1. Interface
Protocols
● MPI Yes; occupies 2 nodes per device (1 x CPU, 1 x OP)
● PROFIBUS DP master No
● PROFIBUS DP device No
MPI
● Number of nodes, max. 32; PG/PC, OP, C7, S7-300/400, M7
● Transmission rate, max. 187.5 kbit/s
communication functions / header
S7 communication
● S7 extended communication Yes; Server
S5 compatible communication
● supported Yes
Standard communication (FMS)
● supported Yes
Number of connections
● overall
— of which dynamic 8
— of which static 4
Interrupts/diagnostics/status information
Diagnostics function Yes; C7-CPU
Substitute values connectable Yes; Parameterizable
Alarms
● Alarm cycle Yes; Parameterizable
● Diagnostic alarm Yes; Measurement overrange, wire break detection at 4 to 20 mA by means of software; parameterizable for parameter errors
Counter
Number of counter inputs 3; UE1, UE2, UE3
Principle Counting of edges
Counting range, description UI1, UI2: up: 0 to 65535, down: 65535 to 0; UI3: up: 0 to 16777215, down: 16777215 to 0
Counter frequency, max. 10 kHz
Counting alarm backward counter on reaching "0"
Counting alarm forward counter on reaching limit value
Enable In the program
Limit value (setpoint) default one counter per value
External gate counters
● Number of external gate counters 3
● Principle Counting of edges within a gate time via external pin
● Counting range UE1, UE2: 0 to 65535; UE3: 0 to 16777215
Frequency counter
● Number 1; UI3
● Principle Counting of pulses within a time period
● Gate width, adjustable Yes
● Gate width 0.1 / 1 / 10 s (adjustable)
● Counting range 0 to 16777215
Cycle duration counter
● Number 1; UI3
● Cycle duration, max. 8.38 s; or 0.12 Hz
● Principle Counting of fixed time units between two positive edges
● Counting range, lower limit 0
● Counting range, upper limit 16 777 214
Potential separation
Potential separation digital inputs
● Potential separation digital inputs Yes; Optocoupler
● between the channels, in groups of 16
Potential separation digital outputs
● Potential separation digital outputs Yes; Optocoupler
● between the channels, in groups of 8
Potential separation analog inputs
● Potential separation analog inputs Yes; shared with AO
Potential separation analog outputs
● Potential separation analog outputs Yes; shared with AI
Potential separation channels
● Potential separation universal inputs No
Isolation
Isolation tested with 500 V DC
EMC
EMC interference immunity Noise immunity: IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4, IEC 1000-4-6, EN 50140
Emission of radio interference acc. to EN 55 022
● Interference emission acc. to EN 55022, class A Yes; Noise emission: Class A / EN 55022; conducted interference: IEC 1000-4-4, IEC 1000-4-5
Degree and class of protection
IP (at the front) IP65
IP (rear) IP20
Standards, approvals, certificates
CSA approval Yes; to Standard C22.2 number 142
UL approval Yes; UL 508
FM approval Yes; FM-Standards No. 3611, 3600, 3810 Class I, Division 2, Group A, B, C, D
developed in accordance with IEC 61131 Yes; EN 61131-2 (IEC 1131-2)
DIN/ISO 9001 Yes
Ambient conditions
Ambient temperature during operation
● vertical installation, min. 0 °C
● vertical installation, max. 50 °C
Air pressure acc. to IEC 60068-2-13
● permissible range, lower limit 795 hPa
● permissible range, upper limit 1 080 hPa
Relative humidity
● Operation, min. 5 %
● Operation, max. 95 %; no condensation
Vibrations
● Operation, tested according to IEC 60068-2-6 Yes; IEC 60068-2-6; 10 Hz to 58 Hz; (constant amplitude 0.075 mm); 58 Hz to 500 Hz; (constant acceleration 9.8 m/s²)
Shock testing
● tested according to IEC 60068-2-29 Yes; IEC 68, Part 2-29 half-sine: 100 m/s² (10 g), 16 ms, 100 shocks
configuration / header
Configuration software
● STEP 7 Yes
● STEP 7 Lite Yes
● ProTool Yes
● ProTool/Lite Yes
● ProTool/Pro Yes
configuration / programming / header
● Command set see instruction list
● Nesting levels 8
● Program organization Linear, structured
● System functions (SFC) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Software libraries
— Process diagnostics Yes; C7-CPU
— Software controller Yes; 16 circles
Know-how protection
● User program protection/password protection Yes
— Password levels 9
programming / cycle time monitoring / header
● lower limit 1 ms
● upper limit 6 000 ms
● adjustable Yes
● preset 150 ms
Languages
Online languages
● Number of online/runtime languages 3
Functionality under WinCC (TIA Portal)
Message system
● Number of messages 499
● Number of process values per message 8
Recipe management
● Number of recipes 99
● Data records per recipe 99
● Entries per data record 99
● recipe memory, max. 4 kbyte
Images
● Number of configurable images 99
Image objects
● Number of I/O fields per image 99
● Graphics object
— Character graphics Yes; As part of the character set
Complex image objects
● dynamic objects Input, output, input/output fields, date/time fields, symbolic input/output fields
Dimensions
Width 240 mm
Height 203.5 mm
Depth 90 mm
Mounting cutout, width 231 mm
Mounting cutout, height 159 mm
Weights
Weight, approx. 1 800 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Quality & warranty

Outstanding service quality with every handle

Two Eichler technicians high-five each other after a successful repair

Your shopping basket

Loading shopping basket