SIEMENS 6EP1336-1LB00

  • EICHLER-art.no.: K1138831
  • EAN: 4025515154549

Product description

SITOP PSU100L 24 V/20 A Geregelte Stromversorgung Eingang: AC 100-240 V Ausgang: DC 24 V/20 A

Services for SIEMENS 6EP1336-1LB00

Repair

2-5 days

from 183,60 €

to 280,80 €

Replacement

Used

New

Delivery information
Export identifier AL: N ECCN: EAR99
Net weight 1.8
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4025515154549
UPC /
Static lot number 85044083
List indicator KT10-PH
Product group 4219
Country of origin CN
Compliance with the substance restrictions according to RoHS directive Since: 20991231
Product classifications Version Classification
eClass 4 /
eClass 5.1 /
eClass 6.0 27-04-90-02
ETIM 3 /
ETIM 4 /
ETIM 5 EC002540

Attribute Value
General information
Technical Product Detail Page https://i.siemens.com/1P6EP1336-1LB00
input
type of the power supply network 1-phase AC or DC
supply voltage at AC
● minimum rated value 100 V
● maximum rated value 240 V
● initial value 85 V
● full-scale value 264 V
supply voltage at DC 100 ... 240 V
input voltage at DC 88 ... 370 V
wide range input Yes
buffering time for rated value of the output current in the event of power failure minimum 20 ms
operating condition of the mains buffering at Vin = 93/187 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 5.55 A
● at rated input voltage 230 V 2.35 A
current limitation of inrush current at 25 °C maximum 45 A
duration of inrush current limiting at 25 °C
● typical 15 ms
I2t value maximum 3.3 A²·s
fuse protection type T 10 A/250 V (not accessible)
fuse protection type in the feeder Recommended miniature circuit breaker: from 10 A characteristic C
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 22.8 ... 26.4 V
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 1 %
residual ripple
● maximum 150 mV
● typical 50 mV
voltage peak
● maximum 240 mV
● typical 100 mV
display version for normal operation Green LED for 24 V OK
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 20 ms
output current
● rated value 20 A
● rated range 0 ... 20 A; +45 ... +70 °C: Derating 2.5%/K
supplied active power typical 480 W
bridging of equipment Yes
number of parallel-switched equipment resources for increasing the power 2
efficiency
efficiency in percent 92 %
power loss [W]
● at rated output voltage for rated value of the output current typical 45 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.5 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical 3 %
setting time
● load step 10 to 90% typical 0.7 ms
● load step 90 to 10% typical 6 ms
protection and monitoring
design of the overvoltage protection < 33 V
property of the output short-circuit proof Yes
design of short-circuit protection Constant current characteristic
● typical 24 A
enduring short circuit current RMS value
● typical 24 A
safety
galvanic isolation between input and output Yes
galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.8 mA
protection class IP IP20
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● EAC approval Yes
● NEC Class 2 No
type of certification
● BIS Yes; R-41184349
● CB-certificate Yes
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval No
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) No
● French marine classification society (BV) No
● Det Norske Veritas (DNV) No
● Lloyds Register of Shipping (LRS) No
ambient conditions
ambient temperature
● during operation -25 ... +70 °C; with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection screw terminal
● at input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
● at output +, -: 2 screw terminals each for 0.5 ... 2.5 mm²
● for auxiliary contacts -
mechanical data
width × height × depth of the enclosure 110 × 125 × 125 mm
installation width × mounting height 110 mm × 225 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
● DIN-rail mounting Yes
● S7 rail mounting No
● wall mounting No
housing can be lined up Yes
net weight 1.8 kg

Important documents