| General information |
|
| Product type designation |
IM 153-4 PN ST |
| Vendor identification (VendorID) |
002AH |
| Device identifier (DeviceID) |
0302H |
| Supply voltage |
|
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| external protection for power supply lines (recommendation) |
In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) |
| Mains buffering |
|
| ● Mains/voltage failure stored energy time |
5 ms |
| Input current |
|
| Current consumption, max. |
600 mA; with 24 V DC supply |
| Inrush current, typ. |
4 A |
| I²t |
0.09 A²·s |
| Output voltage |
|
| Rated value (DC) |
5 V |
| Output current |
|
| for backplane bus (5 V DC), max. |
1.5 A |
| Power loss |
|
| Power loss, typ. |
6 W |
| Address area |
|
| Addressing volume |
|
| ● Inputs |
192 byte |
| ● Outputs |
192 byte |
| Hardware configuration |
|
| number of modules per DP device interface, max. |
12 |
| Protocols |
|
| Bus protocol/transmission protocol |
PROFINET IO |
| Protocols (Ethernet) |
|
| ● TCP/IP |
No |
| Redundancy mode |
|
| ● PROFINET system redundancy (S2) |
No |
| Media redundancy |
|
| — MRP |
Yes |
| Interrupts/diagnostics/status information |
|
| Diagnostics indication LED |
|
| ● LINK LED |
Yes; green LED |
| ● RX/TX LED |
Yes; Yellow LED |
| ● for module diagnostics |
Yes |
| Potential separation |
|
| Potential separation exists |
Yes |
| Isolation |
|
| Isolation tested with |
500 V DC |
| Degree and class of protection |
|
| IP degree of protection |
IP20 |
| Ambient conditions |
|
| Ambient temperature during operation |
|
| ● min. |
0 °C |
| ● max. |
60 °C |
| Altitude during operation relating to sea level |
|
| ● Installation altitude above sea level, max. |
2 000 m |
| Dimensions |
|
| Width |
40 mm |
| Height |
125 mm |
| Depth |
118 mm |
| Weights |
|
| Weight, approx. |
215 g |