SIEMENS 6AG1321-1BH02-2AA0

  • EICHLER-art.no.: K0169906
  • EAN: 4025515136156
  • UPC: 662643199031

Product description

SIPLUS S7-300 SM321 - 20-POLE -40 ... +70 DGR C WITH CONFORMAL COATING CONFORMITY WITH EN50155 T1 KAT 1 KL A/B BASED ON 6ES7321-1BH02-0AA0 . DIGITAL INPUT OPTIC. ISOLATED 16 DI, 24V DC, 1 X 20-POLE

Services for SIEMENS 6AG1321-1BH02-2AA0

Repair

2-5 days

from 364,65 €

to 557,70 €

Replacement

Used

New

Delivery information
Export identifier AL: N ECCN: EAR99H
Net weight 0.238
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4025515136156
UPC 662643199031
Static lot number 85389091
List indicator A&DSE/SIP ADD
Product group 4398
Country of origin DE
Compliance with the substance restrictions according to RoHS directive Since: 20120101
Product classifications Version Classification
eClass 4 27-24-03-04
eClass 5.1 27-24-22-04
eClass 6.0 27-24-22-04
ETIM 3 /
ETIM 4 EC001419
ETIM 5 EC001419

Attribute Value
General information
based on 6ES7321-1BH02-0AA0
Product function
● Isochronous mode No
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 10 mA
Power loss
Power loss, typ. 3.5 W
Digital inputs
Number of digital inputs 16
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 16
— up to 60 °C, max. 16; 16 @ > 60 °C
vertical installation
— up to 40 °C, max. 16
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal "0" -30 to +5 V
● for signal "1" 13 to 30V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable No
— at "0" to "1", min. 1.2 ms
— at "0" to "1", max. 4.8 ms
— at "1" to "0", min. 1.2 ms
— at "1" to "0", max. 4.8 ms
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Interrupts/diagnostics/status information
Alarms No
Diagnostics function No
Alarms
● Diagnostic alarm No
● Hardware interrupt No
Diagnostics indication LED
● Status indicator digital input (green) Yes
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels, in groups of 16
● between the channels and backplane bus Yes; Optocoupler
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50155 Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007 (see SIOS entry 109755985)
Ambient conditions
Ambient temperature during operation
● min. -40 °C; = Tmin
● max. 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5 Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5 Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
— to mechanically active substances according to EN 60721-3-5 Yes; Class 5S3 incl. sand, dust; *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6 Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6 Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6 Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4 Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 * The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 200 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket