| General information |
|
| Usable terminal block |
TB6/AC |
| Supply voltage |
|
| Rated value (AC) |
120/230 V AC |
| Line frequency |
|
| ● permissible range, lower limit |
47 Hz |
| ● permissible range, upper limit |
63 Hz |
| Input current |
|
| Current consumption, typ. |
60 mA |
| Power loss |
|
| Power loss, typ. |
6 W; at 230 V; 4.5 W at 120 V |
| Digital inputs |
|
| Number of digital inputs |
16 |
| Input voltage |
|
| ● Rated value (AC) |
120/230 V AC |
| ● for signal "0" |
0 to 40V |
| ● for signal "1" |
79 to 264V |
| Input current |
|
| ● for signal "1", typ. |
10.5 mA; At 230 V AC/50 Hz and 6.5 mA at 120 V AC/50 Hz |
| Input delay (for rated value of input voltage) |
|
| for standard inputs |
|
| — at "0" to "1", min. |
0 ms |
| — at "0" to "1", max. |
25 ms |
| Cable length |
|
| ● unshielded, max. |
600 m |
| Encoder |
|
| Connectable encoders |
|
| ● 2-wire sensor |
No |
| — permissible quiescent current (2-wire sensor), max. |
2 mA |
| Interfaces |
|
| PROFIBUS DP |
|
| ● Transmission rate, max. |
12 Mbit/s |
| Protocols |
|
| Bus protocol/transmission protocol |
PROFIBUS DP |
| Interrupts/diagnostics/status information |
|
| Diagnostics indication LED |
|
| ● RUN LED |
Yes |
| ● Bus fault BF (red) |
Yes |
| ● Status indicator digital input (green) |
Yes |
| Potential separation |
|
| between electronic block and PROFIBUS DP |
Yes; 500 V DC to the logic, 1 500 V AC to connecting terminals |
| Potential separation digital inputs |
|
| ● Potential separation digital inputs |
Yes; Optocoupler |
| ● between the channels, in groups of |
4 |
| Ambient conditions |
|
| Ambient temperature during operation |
|
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C; 40°C for other mountings |
| Air pressure acc. to IEC 60068-2-13 |
|
| ● permissible range, lower limit |
795 hPa |
| ● permissible range, upper limit |
1 080 hPa |
| Relative humidity |
|
| ● Operation, min. |
15 % |
| ● Operation, max. |
95 %; RH class 2 in accordance with IEC 1131-2 |
| Vibrations |
|
| ● Operation, tested according to IEC 60068-2-6 |
Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
| Shock testing |
|
| ● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
| Connection method |
|
| Design of electrical connection for the inputs and outputs |
Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
| Dimensions |
|
| Width |
235 mm; EB and TB |
| Height |
130 mm; EB and TB |
| Depth |
60 mm; EB and TB |
| Weights |
|
| Weight, approx. |
811 g; EB and TB |