SIEMENS 3RK2200-0CQ30-0AA3

  • EICHLER-art.no.: K0145588
  • EAN: 4011209660366
  • UPC: 040892547207

Product description

AS-I COMPACT MODULE K20, IP67, A/B-SLAVE, DIGITAL, 4DI, 4 X INPUT FOR SENSOR(MECHAN./2- OR 3-WIRE) PNP, SENSOR SUPPLY FROM U_ASI TOTAL MAX.200MA, 2XM12-SOCKET

Services for SIEMENS 3RK2200-0CQ30-0AA3

Repair

2-5 days

from 130,05 €

to 198,90 €

Replacement

Used

New

1-3 days

1 Pcs.

152,00 €

144,40 €

144,40 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: N
Net weight 0.088
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4011209660366
UPC 040892547207
Static lot number 85371098
List indicator CC-IC10
Product group 3720
Country of origin CZ
Compliance with the substance restrictions according to RoHS directive Since: 20060701
Product classifications Version Classification
eClass 4 27-24-21-05
eClass 5.1 27-24-26-04
eClass 6.0 27-24-26-04
ETIM 3 /
ETIM 4 EC001599
ETIM 5 EC001599

Attribute Value
General technical data
design of the product digital I/O modules for operation in the field, IP67 - K20
design of the device type A/B slave
type of electrical connection of the inputs and outputs M12 screw-type terminals
Sensor supply
type of voltage supply for sensor supply using AS-Interface
input voltage 16.5 ... 30 V
property of the sensor supply short-circuit and overload resistant Yes
ampacity of the sensor supply for all inputs
● at ambient temperature 40 °C 200 mA
● at ambient temperature 55 °C 150 mA
Inputs
number of digital inputs 4
type of connection technology 2- and 3-wire technology
type of voltage of the input voltages DC
input current at digital input
● for signal <1> minimum 6 mA
● with signal <0> maximum 1.5 mA
design of the pin assignment of the inputs Y assignement
Outputs
number of digital outputs 0
Ambient conditions
ambient temperature
● during operation -25 ... +70 °C
● during storage -40 ... +85 °C
protection class IP IP67
Mechanical data
width 20 mm
height 108 mm
depth 45 mm
fastening method no mounting plate required
shock resistance 15 g / 11 ms

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket