Product description

AS-i compact module K60 digital 8 DI, IP67 8 x inputs, maximum 200 mA 8 x M12 socket Y-II assignment Mounting plate 3RK1901-0CA00 must be ordered separately

Services for SIEMENS 3RK1200-0DQ00-0AA3

Repair

2-5 days

from 252,45 €

to 386,10 €

Replacement

Used

New

1-3 days

2 Pcs.

296,00 €

281,20 €

281,20 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: N
Net weight 0.19
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4011209325920
UPC 754554432267
Static lot number 85371098
List indicator CC-IC10
Product group 3720
Country of origin CZ
Compliance with the substance restrictions according to RoHS directive Since: 20120501
Product classifications Version Classification
eClass 4 27-24-21-05
eClass 5.1 27-24-26-04
eClass 6.0 27-24-26-04
ETIM 3 /
ETIM 4 EC001599
ETIM 5 EC001599

Attribute Value
General technical data
design of the product digital I/O modules for operation in the field, IP67 - K60
design of the device type standard slave
type of electrical connection of the inputs and outputs M12 screw-type terminals
Sensor supply
type of voltage supply for sensor supply using AS-Interface
input voltage 20 ... 30 V
property of the sensor supply short-circuit and overload resistant Yes
ampacity of the sensor supply for all inputs
● at ambient temperature 40 °C 200 mA
Inputs
number of digital inputs 8
type of connection technology 2- and 3-wire technology
type of voltage of the input voltages DC
input current at digital input
● for signal <1> minimum 6 mA
● with signal <0> maximum 1.5 mA
design of the pin assignment of the inputs Y-II assignement
Outputs
number of digital outputs 0
design of the pin assignment of the outputs Y-II assignement
Ambient conditions
ambient temperature
● during operation -25 ... +85 °C
● during storage -40 ... +85 °C
protection class IP IP67
Mechanical data
width 60 mm
height 152 mm
depth 29 mm
fastening method standard rail mounting/wall mounting using mounting plate for K60 compact module
shock resistance 15 g / 11 ms

Important documents