SIEMENS 6AV3617-1JC20-0AX1
-
SIEMENS | HMI | Operator Panels
- EICHLER-art.no.: K0116661
- EAN: 4025515052135
Product description
OPERATOR PANEL OP 17/DP LC DISPLAY, LED BACKLIT 4X 20/8X 40 LINES X CHARACTERS SIMATIC S7, M7, PROFIBUS DP 1.5 MBAUD WITH UL/CSA APPROVAL
Services for SIEMENS 6AV3617-1JC20-0AX1
SIEMENS |
6AV3617-1JC20-0AX1 –
additional product information
| Delivery information | |||
|---|---|---|---|
| Export identifier | AL: ECCN: | ||
| Net weight | 0.56 | ||
| Quantity | 1 Stück | ||
| Packaging quantity | 1 | ||
| Additional product information | |||
|---|---|---|---|
| Product status | EOP: 2007-10-01 | ||
| EAN | 4025515052135 | ||
| UPC | / | ||
| Static lot number | 85371098 | ||
| List indicator | / | ||
| Product group | 4368 | ||
| Country of origin | DE | ||
| Compliance with the substance restrictions according to RoHS directive | Since: / | ||
| Product classifications | Version | Classification | |
|---|---|---|---|
| eClass | 4 | / | |
| eClass | 5.1 | / | |
| eClass | 6.0 | / | |
| ETIM | 3 | / | |
| ETIM | 4 | / | |
| ETIM | 5 | / | |
What is the 6AV3617-1JC20-0AX1 (OP 17/DP)?
The 6AV3617-1JC20-0AX1 is a SIMATIC OP 17/DP operator panel, typically supplied as a spare part. It is a classic text-based HMI panel for machine operation and monitoring via key-based input and line display. It is especially used in legacy systems where the original OP17 operating concept must be maintained without redesign or migration.
Technical key data at a glance
The panel operates on 24 V DC (approx. 10 W) and has a front protection rating of IP65. For replacement and installation, key dimensions include a front cut-out of 240 × 204 mm and an installation depth of 50 mm.
Display: monochrome line display (4×20 / 8×40)
The OP 17/DP uses a black-and-white LC line display supporting up to 8 lines with 40 characters per line. The LED backlight has an estimated MTBF of around 200,000 hours (at 25 °C), which is particularly relevant for long-term replacement strategies when displays become dim or fail.
Operation: keys, function keys & LEDs
Operation is performed via a membrane keyboard with 24 function keys (16 with LEDs) and configurable labels. This is critical in systems where the machine logic is based on fixed operator functions such as start, stop, and acknowledge.
Communication: PROFIBUS-DP 1.5 Mbit/s (RS485)
The device communicates via PROFIBUS-DP over RS485 up to 1.5 Mbit/s, making it suitable for classic SIMATIC S7/M7 environments where PROFIBUS remains in use.
Interfaces & memory: RS232/RS422, 256 kB user data
The panel provides 2× RS232, 1× RS422, and 1× RS485 (DP bus), along with 256 kB user memory. It does not support Industrial Ethernet.
Engineering software: ProTool/Lite (from V2.51)
Configuration is performed using ProTool / ProTool Lite (from version 2.51). For legacy installations, this software compatibility is often a key factor for continued operation and maintenance.
Repair/exchange: lead time, test report, warranty
For fast restoration of operation, EICHLER offers repair within 1–3 days as well as exchange and refurbished units in 1–3 days. A test report (“Operator Panel with Key”) is optionally available, and repairs include full functional testing with a minimum 24-month warranty.
Identification & ordering information
For procurement and clear identification: MPN 6AV3617-1JC20-0AX1, EICHLER article no. K0116661, EAN 4025515052135.
| Display | |
|---|---|
| Design of display | LC display, black/white |
| Line display | |
| ● Number of lines | 8 |
| ● Number of characters per line | 40 |
| Backlighting | |
| ● MTBF backlighting (at 25 °C) | 200 000 h |
| Control elements | |
| Control elements | Keys |
| Keyboard fonts | |
| ● Membrane keyboard | Yes |
| — user-definable label membrane keys | Yes |
| ● Function keys | |
| — Number of function keys | 24 |
| — Number of function keys with LEDs | 16 |
| ● System keys | |
| — Number of system keys | 22 |
| ● Numeric keyboard | Yes |
| ● alphanumeric keyboard | No |
| ● hexadecimal keyboard | Yes |
| ● Multi-key operation | No |
| Installation type/mounting | |
| Mounting position | vertical |
| maximum permissible angle of inclination without external ventilation | 90° |
| Supply voltage | |
| Type of supply voltage | 24 V DC |
| UPS connectable (serial) | No |
| Input current | |
| Current consumption (rated value) | 0.34 A |
| Power | |
| Active power input, typ. | 10 W |
| Processor | |
| Processor type | X86 |
| Drives | |
| Diskette drive | No |
| CD-ROM | No |
| Hard disk | No |
| Memory | |
| Type of memory | Flash / RAM |
| Memory available for user data | 256 kbyte |
| Battery | |
| Backup battery | |
| ● Backup battery (optional) | Yes; optional 3.6 V |
| ● Backup time, min. | 4 y |
| Type of output | |
| Info LED | Yes |
| Power LED | No |
| Error LED | Yes |
| Time of day | |
| Clock | |
| ● Type | Hardware clock, battery backup, synchronizable |
| ● retentive | Yes |
| ● synchronizable | Yes |
| Interfaces | |
| Interfaces/bus type | 2x RS 232, 1x RS 422, 1x RS 485 (max. 1.5 Mbit/s) |
| Number of RS 485 interfaces | 1 |
| USB port | No |
| PC card slot | No |
| CF card slot | No |
| Special interfaces | No |
| Degree and class of protection | |
| IP (at the front) | IP65 |
| IP (rear) | IP20 |
| Standards, approvals, certificates | |
| Certificate of suitability | CE, PRS, FM Class I Div. 2, UL, EX Zone 2/22 |
| Ambient conditions | |
| Ambient temperature during storage/transportation | |
| ● min. | -25 °C |
| ● max. | 70 °C |
| Relative humidity | |
| ● Operation, max. | 95 % |
| Operating systems | |
| pre-installed operating system | Rmos |
| Configuration | |
| Configuration software | |
| ● Configuration tool | ProTool / Lite Version 2.51 or higher (to be ordered separately) |
| Dimensions | |
| Width of the housing front | 240 mm |
| Height of housing front | 204 mm |
| Overall depth | 50 mm |
| Weights | |
| Weight (without packaging) | 0.96 kg |
| Fault description | Possible solution |
|---|---|
| Display is dark or barely readable – what is typical? | In older panels, the backlight is often the root cause. The datasheet specifies a backlight MTBF of approx. 200,000 hours (at 25 °C), so ageing effects after long operating periods are plausible. |
| No PROFIBUS-DP communication – what should be checked first? | Since DP communication runs over RS485, first check termination resistors, connectors, cabling, baud rate, station address, and possible bus interruptions. The DP speed is specified up to 1.5 Mbit/s, and incorrect bus parameters can quickly lead to communication failure. |
| Keys do not respond or LEDs remain off – what are the quick checks? | Verify the project configuration and key assignment, and ensure a stable 24 V DC power supply (rated current approx. 0.34 A). If the failure is reproducible, a tested replacement unit is often the fastest way to confirm whether the hardware is defective. |
| When is replacement more sensible than further troubleshooting? | If operation is production-critical or errors occur repeatedly, a replacement unit (typically available within 1–3 days) is often the more economical solution. An optional paid test report and service warranty can reduce risk and speed up decision-making. |
What is the 6AV3617-1JC20-0AX1 used for?
It is used as an OP 17/DP operator panel for text-based operation and line-by-line visualisation in SIMATIC legacy systems. It is typically deployed as a 1:1 spare part, especially when existing machines must be restored quickly without modifying the original operating concept.
Which display data is critical for replacement?
The panel uses a monochrome LC line display (4×20 / 8×40 characters). The backlight has an estimated MTBF of approx. 200,000 hours (at 25 °C), which is relevant when assessing ageing or low-visibility display issues.
How is the panel connected?
Communication is via PROFIBUS-DP over RS485, with a maximum speed of up to 1.5 Mbit/s.
How many keys does the OP 17/DP have?
It features 24 function keys, including 16 with LEDs, implemented as a membrane keyboard with configurable labels.
How fast are repair or replacement units available?
At EICHLER, repair, exchange, and refurbished units are typically available within 1–3 days, including a minimum 24-month warranty and service guarantee.