SIEMENS 3RW4425-1BC44
- EICHLER-art.no.: K0146233
- EAN: 4011209625433
- UPC: 754554923956
Product description
SIRIUS SOFT STARTER, VALUES WITH 400 V, 40 DEG., STANDARD: 57A, 30KW, INSIDE-DELTA CIRCUIT 3: 99A, 55KW, 200-460 V AC, 230 V AC, SCREW TERMINALS
Services for SIEMENS 3RW4425-1BC44
Repair
from 2.272,50 €
to 2.929,00 €
Replacement
3.413,30 €
3.242,63 €
Used
3.792,55 €
3.602,92 €
New
SIEMENS |
3RW4425-1BC44 –
additional product information
| Delivery information | |||
|---|---|---|---|
| Export identifier | AL: N ECCN: N | ||
| Net weight | 5.69 | ||
| Quantity | 1 Stück | ||
| Packaging quantity | 1 | ||
| Additional product information | |||
|---|---|---|---|
| Product status | EOP: 2022-10-01 | ||
| EAN | 4011209625433 | ||
| UPC | 754554923956 | ||
| Static lot number | 85371098 | ||
| List indicator | CC-IC10 | ||
| Product group | 3728 | ||
| Country of origin | CZ | ||
| Compliance with the substance restrictions according to RoHS directive | Since: 20090528 | ||
| Product classifications | Version | Classification | |
|---|---|---|---|
| eClass | 4 | 27-02-11-01 | |
| eClass | 5.1 | 27-02-41-01 | |
| eClass | 6.0 | 27-37-09-07 | |
| ETIM | 3 | / | |
| ETIM | 4 | EC000640 | |
| ETIM | 5 | EC000640 | |
| Attribute | Value |
|---|---|
| General technical data | |
| product brand name | SIRIUS |
| product designation | Soft starter |
| product feature | |
| ● integrated bypass contact system | Yes |
| ● thyristors | Yes |
| product function | |
| ● intrinsic device protection | Yes |
| ● motor overload protection | Yes |
| ● evaluation of thermistor motor protection | Yes |
| ● external reset | Yes |
| ● adjustable current limitation | Yes |
| ● inside-delta circuit | Yes |
| product component motor brake output | Yes |
| insulation voltage rated value | 690 V |
| degree of pollution | 3, acc. to IEC 60947-4-2 |
| reference code according to EN 61346-2 | Q |
| reference code according to DIN 40719 extended according to IEC 204-2 according to IEC 750 | G |
| Power Electronics | |
| operational current | |
| ● at 40 °C rated value | 57 A |
| ● at 50 °C rated value | 51 A |
| ● at 60 °C rated value | 45 A |
| operational current for 3-phase motors at inside-delta circuit | |
| ● at 40 °C rated value | 99 A |
| ● at 50 °C rated value | 88 A |
| ● at 60 °C rated value | 78 A |
| yielded mechanical performance for 3-phase motors | |
| ● at 230 V | |
| — at standard circuit at 40 °C rated value | 15 kW |
| — at inside-delta circuit at 40 °C rated value | 30 kW |
| ● at 400 V | |
| — at standard circuit at 40 °C rated value | 30 kW |
| — at inside-delta circuit at 40 °C rated value | 55 kW |
| yielded mechanical performance [hp] for 3-phase AC motor at 200/208 V at standard circuit at 50 °C rated value | 15 hp |
| operating frequency rated value | 50 ... 60 Hz |
| relative negative tolerance of the operating frequency | -10 % |
| relative positive tolerance of the operating frequency | 10 % |
| operating voltage at standard circuit rated value | 200 ... 460 V |
| relative negative tolerance of the operating voltage at standard circuit | -15 % |
| relative positive tolerance of the operating voltage at standard circuit | 10 % |
| operating voltage at inside-delta circuit rated value | 200 ... 460 V |
| relative negative tolerance of the operating voltage at inside-delta circuit | -15 % |
| relative positive tolerance of the operating voltage at inside-delta circuit | 10 % |
| minimum load [%] | 8 % |
| adjustable motor current for motor overload protection minimum rated value | 11 A |
| continuous operating current [% of Ie] at 40 °C | 115 % |
| power loss [W] at operational current at 40 °C during operation typical | 36 W |
| Control circuit/ Control | |
| type of voltage of the control supply voltage | AC |
| control supply voltage frequency 1 rated value | 50 Hz |
| control supply voltage frequency 2 rated value | 60 Hz |
| relative negative tolerance of the control supply voltage frequency | -10 % |
| relative positive tolerance of the control supply voltage frequency | 10 % |
| control supply voltage 1 at AC | |
| ● at 50 Hz rated value | 230 V |
| ● at 60 Hz rated value | 230 V |
| relative negative tolerance of the control supply voltage at AC at 50 Hz | -15 % |
| relative positive tolerance of the control supply voltage at AC at 50 Hz | 10 % |
| relative negative tolerance of the control supply voltage at AC at 60 Hz | -15 % |
| relative positive tolerance of the control supply voltage at AC at 60 Hz | 10 % |
| display version for fault signal | Display |
| Mechanical data | |
| width | 170 mm |
| height | 192 mm |
| depth | 270 mm |
| fastening method | screw fixing |
| mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| required spacing with side-by-side mounting | |
| ● upwards | 100 mm |
| ● at the side | 5 mm |
| ● downwards | 75 mm |
| wire length maximum | 500 m |
| number of poles for main current circuit | 3 |
| Connections/ Terminals | |
| type of electrical connection | |
| ● for main current circuit | box terminal |
| ● for auxiliary and control circuit | screw-type terminals |
| number of NC contacts for auxiliary contacts | 0 |
| number of NO contacts for auxiliary contacts | 3 |
| number of CO contacts for auxiliary contacts | 1 |
| type of connectable conductor cross-sections for main contacts for box terminal using the front clamping point | |
| ● solid | 2.5 ... 16 mm² |
| ● finely stranded with core end processing | 2.5 ... 35 mm² |
| ● finely stranded without core end processing | 4 ... 50 mm² |
| ● stranded | 4 ... 70 mm² |
| type of connectable conductor cross-sections for main contacts for box terminal using the back clamping point | |
| ● solid | 2,5 ... 16 mm² |
| ● finely stranded with core end processing | 2.5 ... 50 mm² |
| ● finely stranded without core end processing | 10 ... 50 mm² |
| ● stranded | 10 ... 70 mm² |
| type of connectable conductor cross-sections for main contacts for box terminal using both clamping points | |
| ● solid | 2x (2.5 ... 16 mm²) |
| ● finely stranded with core end processing | 2x (2.5 ... 35 mm²) |
| ● finely stranded without core end processing | 2x (4 ... 35 mm²) |
| ● stranded | 2x (4 ... 50 mm²) |
| type of connectable conductor cross-sections for AWG cables for main contacts for box terminal | |
| ● using the back clamping point | 10 ... 2/0 |
| ● using the front clamping point | 10 ... 2/0 |
| ● using both clamping points | 2x (10 ... 1/0) |
| type of connectable conductor cross-sections for auxiliary contacts | |
| ● solid | 2x (0.5 ... 2.5 mm²) |
| ● finely stranded with core end processing | 2x (0.5 ... 1.5 mm²) |
| type of connectable conductor cross-sections for AWG cables | |
| ● for auxiliary contacts | 2x (20 ... 14) |
| ● for auxiliary contacts finely stranded with core end processing | 2x (20 ... 16) |
| Ambient conditions | |
| installation altitude at height above sea level | 5 000 m |
| environmental category | |
| ● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
| ● during storage according to IEC 60721 | 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4 |
| ● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ambient temperature | |
| ● during operation | 60 °C |
| ● during storage | -25 ... +80 °C |
| derating temperature | 40 °C |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| UL/CSA ratings | |
| yielded mechanical performance [hp] for 3-phase AC motor | |
| ● at 200/208 V | |
| — at inside-delta circuit at 50 °C rated value | 25 hp |
| ● at 220/230 V | |
| — at standard circuit at 50 °C rated value | 15 hp |
| — at inside-delta circuit at 50 °C rated value | 30 hp |
| ● at 460/480 V | |
| — at standard circuit at 50 °C rated value | 30 hp |
| — at inside-delta circuit at 50 °C rated value | 60 hp |
| contact rating of auxiliary contacts according to UL | B300 / R300 |