| product brand name |
SIRIUS |
| product designation |
Motor starters |
| design of the product |
direct starter |
| product type designation |
M200D |
| product function |
|
| ● on-site operation |
No |
| ● control circuit interface to parallel wiring |
No |
| insulation voltage rated value |
500 V |
| degree of pollution |
3 |
| surge voltage resistance rated value |
6 000 V |
| maximum permissible voltage for protective separation |
|
| ● between main and auxiliary circuit |
400 V |
| ● between control and auxiliary circuit |
24 V |
| shock resistance |
12 g / 11 ms |
| vibration resistance |
7 mm / 2 g |
| mechanical service life (operating cycles) of the main contacts typical |
10 000 000 |
| type of coordination |
2 |
| Substance Prohibitance (day/month/year) |
38724 |
| SVHC substance name |
Lead CAS-No. 7439-92-1 |
|
Lead monoxide (lead oxide) CAS-No. 1317-36-8 |
|
2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 |
|
Melamine CAS-No. 108-78-1 |
|
6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1 |
| Net Weight |
2.792 kg |
| product function |
|
| ● direct start |
Yes |
| ● reverse starting |
No |
| product component motor brake output |
No |
| product feature |
|
| ● brake control with 230 V AC |
No |
| ● brake control with 400 V AC |
No |
| ● brake control with 24 V DC |
No |
| ● brake control with 180 V DC |
No |
| ● brake control with 500 V DC |
No |
| product extension braking module for brake control |
No |
| product function short circuit protection |
Yes |
| design of short-circuit protection |
circuit-breakers |
| maximum short-circuit current breaking capacity (Icu) |
|
| ● at 400 V rated value |
50 000 A |
| ● at 500 V rated value |
50 000 A |
| EMC emitted interference according to IEC 60947-1 |
CISPR11, ambience A (industrial sector) |
| EMC immunity according to IEC 60947-1 |
corresponds to degree of severity 3, ambience A (industrial sector) |
| conducted interference |
|
| ● due to burst according to IEC 61000-4-4 |
2 kV network connection / 1 kV control connection |
| ● due to conductor-earth surge according to IEC 61000-4-5 |
2 kV |
| ● due to conductor-conductor surge according to IEC 61000-4-5 |
1 kV |
| Safety related data |
|
| proportion of dangerous failures |
|
| ● with low demand rate according to SN 31920 |
50 % |
| ● with high demand rate according to SN 31920 |
75 % |
| B10 value with high demand rate according to SN 31920 |
1 000 000 |
| failure rate [FIT] with low demand rate according to SN 31920 |
100 FIT |
| IEC 61508 |
|
| T1 value for proof test interval or service life according to IEC 61508 |
20 a |
| Electrical Safety |
|
| touch protection against electrical shock |
finger-safe |
| Main circuit |
|
| number of poles for main current circuit |
3 |
| design of the switching contact |
electromechanical |
| adjustable current response value current of the current-dependent overload release |
0.15 ... 2 A |
| type of the motor protection |
full motor protection |
| operating voltage rated value |
200 ... 440 V |
| operational current |
|
| ● at AC at 400 V rated value |
2 A |
| ● at AC-3 at 400 V rated value |
2 A |
| operating power |
|
| ● at AC-3 |
|
| — at 400 V rated value |
0.75 kW |
| — at 500 V rated value |
750 W |
| ● at AC-3e |
|
| — at 400 V rated value |
1 kW |
| — at 500 V rated value |
0.75 kW |
| product function |
|
| ● digital inputs parameterizable |
No |
| ● digital outputs parameterizable |
No |
| number of digital inputs |
4 |
| number of sockets |
|
| ● for digital output signals |
1 |
| ● for digital input signals |
4 |
| number of digital outputs |
1 |
| Supply voltage |
|
| type of voltage of the supply voltage |
DC |
| supply voltage 1 at DC |
24 V |
| supply voltage 1 at DC rated value |
30 V |
| ● minimum permissible |
26.5 V |
| ● maximum permissible |
31.6 V |
| Control circuit/ Control |
|
| type of voltage of the control supply voltage |
DC |
| control supply voltage at DC rated value |
20.4 ... 28.8 V |
| control supply voltage 1 at DC rated value |
24 V |
| control supply voltage 1 at DC rated value |
20.4 ... 28.8 V |
| control supply voltage 1 at DC |
20.4 ... 28.8 V |
| control current at DC |
|
| ● in standby mode of operation |
100 mA |
| ● during operation |
600 mA |
| power loss [W] in auxiliary and control circuit |
|
| ● in switching state OFF with bypass circuit |
2.0736 W |
| ● in switching state ON with bypass circuit |
4.1184 W |
| Response times |
|
| ON-delay time |
85 ms |
| OFF-delay time |
65 ms |
| mounting position |
vertical, horizontal, flat |
| mounting position recommended |
horizontal |
| fastening method |
screw fixing |
| height |
215 mm |
| width |
294 mm |
| depth |
159 mm |
| Ambient conditions |
|
| installation altitude at height above sea level maximum |
2 000 m |
| ambient temperature |
|
| ● during operation |
-25 ... +55 °C |
| ● during storage |
-40 ... +70 °C |
| ● during transport |
-40 ... +70 °C |
| relative humidity during operation |
10 ... 95 % |
| protocol is supported |
|
| ● PROFIBUS DP protocol |
No |
| ● PROFINET protocol |
No |
| design of the interface |
|
| ● AS-Interface protocol |
Yes |
| ● PROFINET protocol |
No |
| ● PROFIBUS DP protocol |
No |
| product function bus communication |
Yes |
| protocol is supported AS-Interface protocol |
Yes |
| product function control circuit interface with IO link |
No |
| type of electrical connection of the communication interface |
M12 plug |
| type of electrical connection |
|
| ● for main current circuit |
plug according to ISO 23570, HAN Q4/2 |
| ● for auxiliary and control circuit |
connector |
| type of electrical connection |
|
| ● 1 for digital input signals |
M12 socket |
| ● 1 for digital output signals |
M12 socket |
| ● 2 for digital input signals |
M12 socket |
| ● 3 for digital input signals |
M12 socket |
| ● 4 for digital input signals |
M12 socket |
| type of electrical connection |
|
| ● at the manufacturer-specific device interface |
optical interface |
| ● for device addressing |
M12 plug |
| ● for supply voltage line-side |
M12 plug |
| full-load current (FLA) for 3-phase AC motor at 480 V rated value |
1.6 A |
| yielded mechanical performance [hp] |
|
| ● for 3-phase AC motor |
|
| — at 460/480 V rated value |
0.7 hp |
| — at 575/600 V rated value |
1 hp |
| operating voltage at AC at 60 Hz according to CSA and UL rated value |
600 V |