| Attribute |
Value |
| Vendor identification (VendorID) |
803Dh |
| Supply voltage |
|
| Load voltage 1L+ |
|
| ● Rated value (DC) |
24 V |
| ● Short-circuit protection |
Yes; Electronic |
| ● Reverse polarity protection |
Yes |
| Load voltage 2L+ |
|
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
No |
| Input current |
|
| from supply voltage 1L+, max. |
180 mA |
| Encoder supply |
|
| Number of outputs |
4 |
| Short-circuit protection |
Yes; Electronic |
| Output current |
|
| ● up to 40 °C, max. |
0.9 A |
| ● up to 55 °C, max. |
0.7 A |
| Power loss |
|
| Power loss, typ. |
3.5 W |
| Hardware configuration |
|
| Expansion modules |
|
| ● Number of expansion modules, max. |
7 |
| — of which motor starters/frequency converters, max. |
6 |
| — of which pneumatic interfaces, max. |
6 |
| Digital inputs |
|
| Number of digital inputs |
8 |
| Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
| Number of simultaneously controllable inputs |
|
| all mounting positions |
|
| — up to 55 °C, max. |
8 |
| Input voltage |
|
| ● Rated value (DC) |
24 V |
| ● for signal "0" |
-3 to +5V |
| ● for signal "1" |
13 to 30V |
| Input current |
|
| ● for signal "1", typ. |
7 mA |
| Input delay (for rated value of input voltage) |
|
| for standard inputs |
|
| — at "0" to "1", min. |
1.2 ms |
| — at "0" to "1", max. |
4.8 ms |
| — at "1" to "0", min. |
1.2 ms |
| — at "1" to "0", max. |
4.8 ms |
| Cable length |
|
| ● unshielded, max. |
30 m |
| Encoder |
|
| Connectable encoders |
|
| ● 2-wire sensor |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
1.5 mA |
| 1. Interface |
|
| Protocols |
|
| ● PROFIBUS DP slave |
Yes |
| PROFIBUS DP slave |
|
| ● Transmission rate, max. |
12 Mbit/s |
| Services |
|
| — Direct data exchange (slave-to-slave communication) |
Yes |
| Protocols |
|
| PROFIBUS DP |
Yes |
| PROFIBUS DP |
|
| Services |
|
| — SYNC capability |
Yes |
| — FREEZE capability |
Yes |
| Interrupts/diagnostics/status information |
|
| Diagnostics function |
Parameterizable |
| Alarms |
|
| ● Diagnostic alarm |
Yes |
| Diagnoses |
|
| ● Diagnostic information readable |
Yes |
| Diagnostics indication LED |
|
| ● For load voltage monitoring |
Yes |
| ● Bus fault BF (red) |
Yes |
| ● Group error SF (red) |
Yes |
| ● Status indicator digital input (green) |
Yes |
| ● Monitoring 24 V voltage supply ON (green) |
Yes |
| Potential separation |
|
| between load voltage and all other switching components |
Yes |
| between PROFIBUS DP and all other circuit components |
Yes |
| Potential separation digital inputs |
|
| ● between the channels |
No |
| Potential separation digital outputs |
|
| ● between the channels |
No |
| Permissible potential difference |
|
| between different circuits |
75 V DC/60 V AC |
| Isolation |
|
| Isolation tested with |
500 V DC |
| Dimensions |
|
| Width |
134 mm |
| Height |
110 mm |
| Depth |
55 mm |
| Weights |
|
| Weight, approx. |
500 g |