| General information |
|
| Product type designation |
F-DQ 4x24VDC/2A PM HF |
| usable BaseUnits |
BU type A0 |
| Product function |
|
| ● I&M data |
Yes; I&M0 to I&M3 |
| Engineering with |
|
| ● STEP 7 TIA Portal configurable/integrated from version |
V12 |
| ● STEP 7 configurable/integrated from version |
V5.5 SP3 / - |
| ● PROFINET from GSD version/GSD revision |
V2.31 |
| Supply voltage |
|
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
19.2 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| power supply according to NEC Class 2 required |
No |
| Input current |
|
| Current consumption (rated value) |
75 mA; without load |
| Current consumption, max. |
21 mA; From the backplane bus |
| Output voltage |
|
| Rated value (DC) |
24 V |
| Power |
|
| Power consumption from the backplane bus |
70 mW |
| Power loss |
|
| Power loss, typ. |
4 W |
| Address area |
|
| Address space per module |
|
| ● Inputs |
5 byte |
| ● Outputs |
5 byte |
| Hardware configuration |
|
| Automatic encoding |
Yes |
| ● Electronic coding element type F |
Yes |
| Digital outputs |
|
| Type of digital output |
Transistor |
| Number of digital outputs |
4 |
| Digital outputs, parameterizable |
Yes |
| Short-circuit protection |
Yes |
| ● Response threshold, typ. |
> 3.3 A |
| Open-circuit detection |
Yes |
| ● Response threshold, typ. |
8 mA |
| Overload protection |
Yes |
| ● Response threshold, typ. |
2.9 A |
| Limitation of inductive shutdown voltage to |
Typ. -2x 47 V |
| Controlling a digital input |
Yes; digital output, according to IEC 61131-2, type 2 |
| Switching capacity of the outputs |
|
| ● with resistive load, max. |
2 A |
| ● on lamp load, max. |
10 W |
| Load resistance range |
|
| ● lower limit |
12 Ω |
| ● upper limit |
2 000 Ω |
| Output voltage |
|
| ● for signal "1", min. |
24 V; L+ (-0.5 V) |
| Output current |
|
| ● for signal "1" rated value |
2 A |
| ● for signal "0" residual current, max. |
0.5 mA |
| Switching frequency |
|
| ● with resistive load, max. |
30 Hz; Symmetrical |
| ● with inductive load, max. |
0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| ● on lamp load, max. |
10 Hz; Symmetrical |
| Total current of the outputs |
|
| ● Current per channel, max. |
2 A; note derating data in the manual |
| ● Current per module, max. |
6 A; note derating data in the manual |
| Cable length |
|
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
500 m |
| Interrupts/diagnostics/status information |
|
| Diagnostics function |
Yes; See Chapter "Alarms/diagnostic messages" in the manual |
| Substitute values connectable |
No |
| Alarms |
|
| ● Diagnostic alarm |
Yes |
| ● Hardware interrupt |
No |
| Diagnostics indication LED |
|
| ● RUN LED |
Yes; green LED |
| ● ERROR LED |
Yes; red LED |
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
| ● Channel status display |
Yes; green LED |
| ● for channel diagnostics |
Yes; red LED |
| ● for module diagnostics |
Yes; green/red DIAG LED |
| Potential separation |
|
| Potential separation channels |
|
| ● between the channels |
No |
| ● between the channels and backplane bus |
Yes |
| ● between the channels and the power supply of the electronics |
No |
| Isolation |
|
| Isolation tested with |
707 V DC (type test) |
| Standards, approvals, certificates |
|
| Suitable for safety functions |
Yes |
| Ecological footprint |
|
| ● environmental product declaration |
Yes |
| Global warming potential |
|
| — global warming potential, (total) [CO2 eq] |
88.3 kg |
| — global warming potential, (during production) [CO2 eq] |
13.1 kg |
| — global warming potential, (during operation) [CO2 eq] |
76.6 kg |
| — global warming potential, (after end of life cycle) [CO2 eq] |
-1.37 kg |
| Highest safety class achievable in safety mode |
|
| ● Performance level according to ISO 13849-1 |
PLe |
| ● SIL acc. to IEC 61508 |
SIL 3 |
| Probability of failure (for service life of 20 years and repair time of 100 hours) |
|
| — Low demand mode: PFDavg in accordance with SIL2 |
< 2.00E-04 |
| — Low demand mode: PFDavg in accordance with SIL3 |
< 2.00E-05 |
| — High demand/continuous mode: PFH in accordance with SIL2 |
< 1.00E-08 1/h |
| — High demand/continuous mode: PFH in accordance with SIL3 |
< 1.00E-09 1/h |
| Ambient conditions |
|
| Ambient temperature during operation |
|
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
50 °C |
| Altitude during operation relating to sea level |
|
| ● Installation altitude above sea level, max. |
4 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Dimensions |
|
| Width |
15 mm |
| Height |
73 mm |
| Depth |
58 mm |
| Weights |
|
| Weight, approx. |
57 g |