SIEMENS 6ES7131-4BF00-0AA0

  • EICHLER-art.no.: K0186190
  • EAN: 4025515074687
  • UPC: 662643216929

Product description

SIMATIC DP, 1 ELECTR. MODULE FOR ET 200S, 8 DI DC 24V 15 MM WIDTH, 1 PIECE PER PACKAGING UNIT

Services for SIEMENS 6ES7131-4BF00-0AA0

Repair

2-5 days

from 94,25 €

to 144,14 €

Replacement

Used

New

Delivery information
Export identifier AL: N ECCN: N
Net weight 0.042
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status EOP: 2023-10-01
EAN 4025515074687
UPC 662643216929
Static lot number 85389091
List indicator ST76
Product group 4467
Country of origin CN
Compliance with the substance restrictions according to RoHS directive Since: 20081231
Product classifications Version Classification
eClass 4 27-24-21-05
eClass 5.1 27-24-26-04
eClass 6.0 27-24-26-04
ETIM 3 /
ETIM 4 EC001599
ETIM 5 EC001599

Attribute Value
General information
Product function
● Isochronous mode Yes; TWE = 3000 us
Supply voltage
Rated value (DC) 24 V; From power module
Reverse polarity protection Yes
Input current
from supply voltage L+, max. Dependent on encoder
from backplane bus 3.3 V DC, max. 10 mA
Encoder supply
Number of outputs 0; no encoder supply
Power loss
Power loss, typ. 1.2 W
Address area
Address space per module
● Address space per module, max. 1 byte
Digital inputs
Number of digital inputs 8
Input characteristic curve in accordance with IEC 61131, type 1 Yes; 2-wire sensors connectable
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal "0" -30 to +5 V
● for signal "1" +15 to +30 V
Input current
● for signal "1", typ. 5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable No
— at "0" to "1", min. 2 ms
— at "0" to "1", max. 4.5 ms
— at "1" to "0", min. 2 ms
— at "1" to "0", max. 4.5 ms
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Interrupts/diagnostics/status information
Diagnostics function No
Diagnostics indication LED
● Status indicator digital input (green) Yes
Parameter
Remark 3-byte parameter (not accessible for the user)
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 35 g

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.