SIEMENS 6EP1332-4BA00
-
SIEMENS | HMI | Power Supplies
- EICHLER-art.no.: K0339735
- EAN: 4025515152705
- UPC: 887621053451
Product description
SIMATIC PM 1507 24 V/3 A stabilized power supply for SIMATIC S7-1500 input: 120/230 V AC output: 24 V DC/3 A without Ex approval
Services for SIEMENS 6EP1332-4BA00
Repair
from 131,75 €
to 201,50 €
Replacement
124,95 €
118,70 €
Used
138,83 €
131,89 €
New
154,00 €
146,30 €
SIEMENS |
6EP1332-4BA00 –
additional product information
| Delivery information | |||
|---|---|---|---|
| Export identifier | AL: N ECCN: N | ||
| Net weight | 0.45 | ||
| Quantity | 1 Stück | ||
| Packaging quantity | 1 | ||
| Additional product information | |||
|---|---|---|---|
| Product status | |||
| EAN | 4025515152705 | ||
| UPC | 887621053451 | ||
| Static lot number | 85044083 | ||
| List indicator | KT10-PF | ||
| Product group | 4205 | ||
| Country of origin | RO | ||
| Compliance with the substance restrictions according to RoHS directive | Since: 20121205 | ||
| Product classifications | Version | Classification | |
|---|---|---|---|
| eClass | 4 | / | |
| eClass | 5.1 | 27-04-90-02 | |
| eClass | 6.0 | 27-04-90-02 | |
| ETIM | 3 | / | |
| ETIM | 4 | EC002540 | |
| ETIM | 5 | EC002540 | |
| Attribute | Value |
|---|---|
| General information | |
| Technical Product Detail Page | https://i.siemens.com/1P6EP1332-4BA00 |
| product brand name | SIMATIC |
| product type designation | PM 1507 |
| product designation | S7-1500 Power Module |
| type of current supply | 24 V/3 A |
| input | |
| type of the power supply network | 1-phase AC |
| phase number | 1 |
| voltage curve at input | AC |
| supply voltage at AC | Automatic range selection |
| supply voltage | 120 V/230 V |
| input voltage 1 at AC | 85 ... 132 V |
| input voltage 2 at AC | 170 ... 264 V |
| supply voltage | |
| ● at 50 Hz | 230 V |
| ● at 60 Hz | 120 V |
| line frequency | 50/60 Hz |
| line frequency | 45 ... 65 Hz |
| wide range input | No |
| overvoltage overload capability | 2.3 × Vin rated, 1.3 ms |
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms |
| operating condition of the mains buffering | at Vin = 93/187 V |
| input current | |
| ● at rated input voltage 120 V | 1.4 A |
| ● at rated input voltage 230 V | 0.8 A |
| current limitation of inrush current at 25 °C maximum | 23 A |
| duration of inrush current limiting at 25 °C | |
| ● maximum | 3 ms |
| I2t value maximum | 1.3 A²·s |
| fuse protection type | T 3,15 A/250 V (not accessible) |
| fuse protection type in the feeder | Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C |
| output | |
| voltage curve at output | Controlled, isolated DC voltage |
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| output voltage at DC rated value | 24 V |
| output voltage | |
| ● at output 1 at DC rated value | 24 V |
| output voltage | |
| ● at output 1 at DC | 24 V |
| output voltage adjustable | No |
| relative overall tolerance of the voltage | 1 % |
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % |
| ● on slow fluctuation of ohm loading | 0.1 % |
| residual ripple | |
| ● maximum | 50 mV |
| voltage peak | |
| ● maximum | 150 mV |
| display version for normal operation | LED green for 24 V OK; LED red for error; LED yellow for stand-by |
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| response delay maximum | 1.5 s |
| voltage increase time of the output voltage | |
| ● typical | 10 ms |
| output current | |
| ● rated value | 3 A |
| ● rated range | 0 ... 3 A |
| supplied active power typical | 72 W |
| short-term overload current | |
| ● on short-circuiting during the start-up typical | 12 A |
| ● at short-circuit during operation typical | 12 A |
| duration of overloading capability for excess current | |
| ● on short-circuiting during the start-up | 70 ms |
| ● at short-circuit during operation | 70 ms |
| bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing the power | 2 |
| efficiency | |
| efficiency in percent | 87 % |
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical | 11 W |
| closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1 % |
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 1 % |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3 % |
| setting time | |
| ● load step 10 to 90% typical | 5 ms |
| ● load step 90 to 10% typical | 5 ms |
| ● maximum | 5 ms |
| protection and monitoring | |
| design of the overvoltage protection | Additional control loop, limitation (closed loop control) at < 28.8 V |
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Electronic shutdown, automatic restart |
| response value current limitation | 3.15 ... 3.6 A |
| ● typical | 3.4 A |
| safety | |
| galvanic isolation between input and output | Yes |
| galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class | Class I |
| leakage current | |
| ● maximum | 3.5 mA |
| ● typical | 0.4 mA |
| protection class IP | IP20 |
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B |
| ● for mains harmonics limitation | EN 61000-3-2 |
| ● for interference immunity | EN 61000-6-2 |
| standards, specifications, approvals | |
| certificate of suitability | |
| ● CE marking | Yes |
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
| ● UKCA marking | Yes |
| ● EAC approval | Yes |
| ● Regulatory Compliance Mark (RCM) | Yes |
| ● NEC Class 2 | No |
| type of certification | |
| ● BIS | Yes; R-41183539 |
| ● CB-certificate | Yes |
| MTBF at 40 °C | 1 611 993 h |
| standards, specifications, approvals hazardous environments | |
| certificate of suitability | |
| ● IECEx | No |
| ● ATEX | No |
| ● ULhazloc approval | No |
| ● UKEX | No |
| ● CCC for hazardous zone according to GB standard | No |
| ● FM registration | No |
| standards, specifications, approvals marine classification | |
| shipbuilding approval | Yes |
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| ● French marine classification society (BV) | Yes |
| ● Det Norske Veritas (DNV) | Yes |
| ● Lloyds Register of Shipping (LRS) | No |
| standards, specifications, approvals Environmental Product Declaration | |
| Environmental Product Declaration | Yes |
| global warming potential [CO2 eq] | |
| ● total | 309.9 kg |
| ● during manufacturing | 8.6 kg |
| ● during operation | 300.9 kg |
| ● after end of life | 0.31 kg |
| ambient conditions | |
| ambient temperature | |
| ● during operation | 0 ... 60 °C; with natural convection |
| ● in horizontal mounting position during operation | 0 ... 60 °C |
| ● in vertical mounting position during operation | 0 ... 40 °C |
| ● during transport | -40 ... +85 °C |
| ● during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| connection method | |
| type of electrical connection | Screw-/spring clamp connection |
| ● at input | L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² |
| ● at output | L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm² |
| removable terminal at input | Yes |
| removable terminal at output | Yes |
| mechanical data | |
| width × height × depth of the enclosure | 50 × 147 × 129 mm |
| installation width × mounting height | 50 mm × 205 mm |
| required spacing | |
| ● top | 40 mm |
| ● bottom | 40 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| fastening method | Can be mounted onto S7-1500 rail |
| ● DIN-rail mounting | No |
| ● S7 rail mounting | Yes |
| ● wall mounting | No |
| housing can be lined up | Yes |
| net weight | 0.45 kg |