SIEMENS 6EP1332-4BA00

  • EICHLER-art.no.: K0339735
  • EAN: 4025515152705
  • UPC: 887621053451

Product description

SIMATIC PM 1507 24 V/3 A stabilized power supply for SIMATIC S7-1500 input: 120/230 V AC output: 24 V DC/3 A without Ex approval

Services for SIEMENS 6EP1332-4BA00

Repair

1-3 days

from 131,75 €

to 201,50 €

Replacement

1-3 days

1 Pcs.

124,95 €

118,70 €

118,70 € *

Please enter an offer recipient here.


Used

1-3 days

1 Pcs.

138,83 €

131,89 €

131,89 € *

Please enter an offer recipient here.


New

1-3 days

3 Pcs.

154,00 €

146,30 €

146,30 € *

Please enter an offer recipient here.


Delivery information
Export identifier AL: N ECCN: N
Net weight 0.45
Quantity 1 Stück
Packaging quantity 1
Additional product information
Product status
EAN 4025515152705
UPC 887621053451
Static lot number 85044083
List indicator KT10-PF
Product group 4205
Country of origin RO
Compliance with the substance restrictions according to RoHS directive Since: 20121205
Product classifications Version Classification
eClass 4 /
eClass 5.1 27-04-90-02
eClass 6.0 27-04-90-02
ETIM 3 /
ETIM 4 EC002540
ETIM 5 EC002540

Attribute Value
General information
Technical Product Detail Page https://i.siemens.com/1P6EP1332-4BA00
product brand name SIMATIC
product type designation PM 1507
product designation S7-1500 Power Module
type of current supply 24 V/3 A
input
type of the power supply network 1-phase AC
phase number 1
voltage curve at input AC
supply voltage at AC Automatic range selection
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 170 ... 264 V
supply voltage
● at 50 Hz 230 V
● at 60 Hz 120 V
line frequency 50/60 Hz
line frequency 45 ... 65 Hz
wide range input No
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of power failure minimum 20 ms
operating condition of the mains buffering at Vin = 93/187 V
input current
● at rated input voltage 120 V 1.4 A
● at rated input voltage 230 V 0.8 A
current limitation of inrush current at 25 °C maximum 23 A
duration of inrush current limiting at 25 °C
● maximum 3 ms
I2t value maximum 1.3 A²·s
fuse protection type T 3,15 A/250 V (not accessible)
fuse protection type in the feeder Recommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C
output
voltage curve at output Controlled, isolated DC voltage
product function output voltage controlled Yes
product function output voltage stabilized Yes
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage
● at output 1 at DC 24 V
output voltage adjustable No
relative overall tolerance of the voltage 1 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.1 %
residual ripple
● maximum 50 mV
voltage peak
● maximum 150 mV
display version for normal operation LED green for 24 V OK; LED red for error; LED yellow for stand-by
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 10 ms
output current
● rated value 3 A
● rated range 0 ... 3 A
supplied active power typical 72 W
short-term overload current
● on short-circuiting during the start-up typical 12 A
● at short-circuit during operation typical 12 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 70 ms
● at short-circuit during operation 70 ms
bridging of equipment Yes
number of parallel-switched equipment resources for increasing the power 2
efficiency
efficiency in percent 87 %
power loss [W]
● at rated output voltage for rated value of the output current typical 11 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.1 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical 3 %
setting time
● load step 10 to 90% typical 5 ms
● load step 90 to 10% typical 5 ms
● maximum 5 ms
protection and monitoring
design of the overvoltage protection Additional control loop, limitation (closed loop control) at < 28.8 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
response value current limitation 3.15 ... 3.6 A
● typical 3.4 A
safety
galvanic isolation between input and output Yes
galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.4 mA
protection class IP IP20
EMC
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
● UKCA marking Yes
● EAC approval Yes
● Regulatory Compliance Mark (RCM) Yes
● NEC Class 2 No
type of certification
● BIS Yes; R-41183539
● CB-certificate Yes
MTBF at 40 °C 1 611 993 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No
● UKEX No
● CCC for hazardous zone according to GB standard No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) Yes
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) No
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes
global warming potential [CO2 eq]
● total 309.9 kg
● during manufacturing 8.6 kg
● during operation 300.9 kg
● after end of life 0.31 kg
ambient conditions
ambient temperature
● during operation 0 ... 60 °C; with natural convection
● in horizontal mounting position during operation 0 ... 60 °C
● in vertical mounting position during operation 0 ... 40 °C
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection Screw-/spring clamp connection
● at input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
● at output L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²
removable terminal at input Yes
removable terminal at output Yes
mechanical data
width × height × depth of the enclosure 50 × 147 × 129 mm
installation width × mounting height 50 mm × 205 mm
required spacing
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
fastening method Can be mounted onto S7-1500 rail
● DIN-rail mounting No
● S7 rail mounting Yes
● wall mounting No
housing can be lined up Yes
net weight 0.45 kg

Important documents

Repair accompanying note

Download the repair accompanying note as a PDF, or use the digital repair registration and send your defective modules to the EICHLER Service Centre for repair.

Laughing Eichler technician points to green PDF with special sale of automation technology

Your shopping basket

Loading shopping basket